On= Forewarning light enabled
DSW5= This enables or disables the water hammer.
Off= Water hammer disabled
On= Water hammer enabled
DSW6= This enables or disables braking in the Opening phase.
Off= Braking in the Opening phase disabled. When the limit switch is triggered, the automatic unit
stops.
On= Braking in the Opening phase enabled. When the limit switch is triggered, the automatic unit
slows down.
DSW7= This enables or disables braking in the Closing phase.
Off= Braking in the Closing phase disabled. When the limit switch is triggered, the automatic unit
stops.
On= Braking in the Closing phase enabled. When the limit switch is triggered, the automatic unit
slows down.
DSW8= This enables or disables the motor pickup.
Off= Motor pickup disabled
On= Motor pickup enabled
Note: When the DSW position is changed, one movement should be performed before the new configuration
is activated.
Dip-switch functions "BYPASS"
The "BYPASS" dip-switch allows to short-circuit the normally closed inputs which are not in use.
DSW1= Input, STOP.
Off= Input enabled
On= Input disabled
DSW2= Input, FTC.
Off= Input enabled
On= Input disabled
DSW3= Input, FCA.
Off= Input enabled
On= Input disabled
DSW4= Input, FCC.
Off= Input enabled
On= Input disabled
DSW5= Input, Safety edge.
Off= Safety edge activated
On= No safety edge (Open Jumper J1)
DSW6= Not connected
This control unit carries out the Power circuit integrity test automatically. If a malfunction is detected it stops
and indicates the fault with two rapid flashes of the PGM LED. The activation of the Thermal switch (Motor
switch) is detected as a fault. In this case the LED will indicate the malfunction, and the following checks will
reset the control unit automatically as soon as the thermal protection is off.
Trimmer functions
TCA
This allows the automatic closure time to be adjusted when this is enabled by positioning the
DSW2 Dip-switch on ON. Adjustment can be from a minimum of 1 to a maximum of 250 seconds.
The minimum time is obtained by rotating the trimmer completely anticlockwise.
TL
This allows the working time of the automation to be adjusted. If the limit switches fail, the soft-
ware protection will intervene after this time has elapsed. (Add about 4 sec. to the actual stroke
time of the automation). Adjustment can be from a minimum of 1 to a maximum of 125 seconds.
The minimum time is obtained by rotating the trimmer completely anticlockwise.
POWER It allows the adjustment of the motor operating power.
To obtain the minimum power turn the trimmer completely anti-clockwise.