INSTALLATION
Installation is permanent and must exclusi-
vely be performed by specialised and quali-
fied personnel, following all the instructions
and provisions included in this manual. Cur-
rent regulations must also be met.
2. 1
SUPPLY (fig. 4)
"MURELLE EQUIPE 100-150 BOX (M)"
heat modules, inter-connectible by flange,
are supplied with an external pre-painted
zinc-coated laminate case.
They are complete with supply/return
water manifold fastening screws and
manifold gas, external temperature probe
kit, cascade supply and RS-485 code
8092250 board connection cable.
Available separately:
– Tubes connecting the hydraulic separa-
tor kit code 8101534 for left-hand fixtu-
res for "100-150 BOX (M)".
– Single box (size: 630 x 640 x 1600) for
hydraulic separator, code 8101517 (figu-
re 4)
– Hydraulic separator kit code 8101550
for "100-150 BOX (M)".
SINGLE BOX FOR
HYDRAULIC SEPARATOR AND TUBES CONNECTING
code 8101517
NOTICE: The supply and return of the hydraulic compensator can be positioned on
the right or left-hand side of the box by moving the connection flange secured with
six screws.
– Polypropylene exhaust manifold kit for
indoor installation (purposely treated to
resist weathering when installed out-
doors):
code 8102511 f or "100 BOX (M)"
module
code 8102512 f or "150 BOX (M)"
module
– Exhaust terminal code 8089530 for out-
door installations.
To electrically connect the modules and to
assemble the exhaust for indoor or outdoor
installations, see points 2.6, 2.7 and 2. 1 0 in
this manual.
2.2
INSTALLATION
2.2. 1
Indoors
"MURELLE EQUIPE 100-150 BOX (M)"
heat modules can be installed in boiler
rooms whose size and requirements meet
current regulations.
Furthermore, vents, with surface areas at
BOX CONTENITORE SINGOLO PER
SEPARATORE IDRAULICO E KIT SICUREZZE ISPESL
cod. 8101517
45
630
least 3.000 sq. cm or 5.000 sq. cm for
gas with density over 0.8, must be installed
in the outer walls for room ventilation.
2.2.2
Outdoors
"MURELLE EQUIPE 100-150 BOX (M)"
heat modules can also be installed out-
doors with the specific exhaust for single
module code 8089530.
2.3

SYSTEM CONNECTIONS

To protect the heat system from damaging
corrosion, incrustation or deposits, after
installation it is extremely important to
clean the system using suitable products
such as, for example, Sentinel X300 (new
systems), X400 and X800 (old systems)
or Fernox Cleaner F3.
Complete instructions are provided with
the products but, for further information,
you may dir ectl y cont act SENTINEL
PERFORMANCE SOLUTIONS LTD or FER-
NOX COOKSON ELECTRONICS.
403
640
ES
ENG
FR
Fig. 4
39