Circuit board wiring diagram for energy saving mode
- 3 - T WO-STOP MODE -
USE: This operating mode enables the user to modify the opening width.
The normal opening width is set by means of CO-02 and the minimum opening with by means of CO-20.
Use of a daily/weekly programmer or a thermostat connected to the SYS input, the opening width can be modified according to the season and daily
temperatures.
Circuit board connections: Connect output sensors (INSIDE) and input sensors (OUTSIDE) to terminals CN4-CN5. Set 1 or 2 pairs on the photocell
circuit and then connect the photocells to wires 4-5 (0-LIMIT).
Connect other types of sensors and pushbuttons to wires 5-7 (0-HELP) to enable opening.
Connect a switch, a daily/weekly programmer or a thermostat to wires 5-6 (0-SYS)to enable modification of the door opening width.
An emergency pushbutton can be fitted by connecting it to wires 8-9 (0-STOP).
A switch/selector should also be connected to wires 3-5 (-0V-D/N) to enable selection of the day/night mode.
Programmer parameter setting procedure
Turn on the power supply
Press STOP on the programmer
Press DATA-ENTER - "CO-00" appears on display
Press the up key once - "CO-01" is displayed
Press DATA-ENTER on CO-01 to enter the Options menu
Select option "3" by means of the up/down keys.
Press DATA-ENTER to confirm the selection – "CO-02" appears on display.
Press DATA-ENTER on CO-02.
Set the opening width (max. opening) by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected width – CO-03 appears on display.
Press the up key until CO-20 is displayed
Press DATA-ENTER on CO-20.
Set the opening width in energy saving mode by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected width – CO-21 appears on display.
Press the up key until CO-39 is displayed
Press DATA-ENTER on CO-39.
Enter the door weight by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected value – CO-40 appears on display.
Press RUN on the programmer.
Turn the main door switch off and on again and perform an operation check.
Circuit board wiring diagram for Two Stop operating mode
- 4 - 2-POSITION PUSHBUTTON MODE -
USE: Opening and closing functions are controlled by different pulses to activate the automatic door. When open, the door does not close until a
closing pulse is sent (the automatic closing wait time is disabled). During closing, if the door is re-opened by a signal from a photocell (LIMIT), the
door is shut automatically after opening. If the D/N switch (DAY/NIGHT function) is set to DAY (closed contact), the electric lock is permanently
released and opening via photocells is also enabled. After opening, the door closes automatically. If set to NIGHT (open contact) the electric lock is
enabled and the photocells are enabled during closing only.