OPENING WIDTH 1 (MAXIMUM)
The door opening width is entered in mm. After entering the value, switch
the door off and then on again to enable closing with the set value. Door
movement precision is 1.3 mm
IMPACT SENSITIVIT Y
Control function for correct door movement in the event of
friction/obstacles – DO NOT TOUCH
OPENING SPEED
Enables entry of the maximum opening speed. Depending on the weight
and width of the door, this speed setting may be disabled (door too
heavy/too narrow).
CLOSING SPEED
Closing speed is factory-set by RIB. For safety reasons, this setting must
remain low.
LOW SPEED OPENING
This speed is factory-set by RIB and does not normally require
modification
LOW SPEED CLOSING
This speed is factory-set by RIB and does not normally require
modification
SPEED GAUGE
This corresponds to door closing speed during initial movement
following a power failure. This setting does not normally require
modification
AUTOMATIC CLOSING WAIT TIME
This time can be set from 0.3 ms to maximum 60 seconds
DOOR CLOSING PRESSURE
This value determines the constant pressure applied by the door during
closing. Values from 2 to 4 supply sufficient pressure to enable use of the
door in windy locations. Function 11 must be used to enable pressure.
Although less than the one enabled using function 11, there is always a
constant pressure when closed to avoid the risk of opening by wind
POWER LOCK ACTIVATION DURING CLOSING
A power lock separate from the electric lock can be selected as required.
This function can be enabled by selecting option 1 (enable on completion
of installation only). The lock is enabled when door pressure (CO-10) is
set to minimum 4. In the event of a power failure the power lock is
inhibited. If the user attempts to open the door manually, the motor
automatically activates closure to prevent intrusion.
CO-02
CO-03
CO-04
CO-05
CO-06
CO-07
CO-08
CO-09
CO-10
CO-11
When using the power lock, set the low speed approach during closing to
at least 100 mm to ensure that opening is activated automatically if the
door is forced open manually over the specified distance
SIREN ACTIVATION
The siren can activated/deactivated as required.
If set to option 1 it is enabled, if set to option 2 it is disabled.
ACCELERATION TIME (STARTING TORQUE) ON OPENING
Fast or slow acceleration can be selected as required. This value does not
normally require modification; soft acceleration is recommended
ACCELERATION TIME (STARTING TORQUE) ON CLOSING
Fast or slow acceleration can be selected as required. This value does not
normally require modification; soft acceleration is recommended.
OPERATION FOLLOWING POWER FAILURE
If the battery is connected the door will operate during even during a
power failure.
Option "0" opens the door during a power failure.
Option "1" closes the door during a power failure if the selector/switch
connected to the D/N (day/night) terminal has its contact open (night),
and opens the door if the contact is closed (day). If no selector/switch is
connected to the D/N terminal, the door will close.
- Using the "6-function selector" the user can ensure the door is closed by
enabling the LOCK function. To leave the building it will be necessary to
press the command HELP to open. To return to the building from
outside the user will have to turn an external key selector to operate the
HELP command, and once inside the building the "6-function selector"
must be set to AUTO.
- In the event of power failure (with battery and electric lock without
release cable installed), the user will still be able to enter by turning an
external key selector activating the DAY command (emergency). This
command will release the electric lock and the door will open
automatically. The user will be able to enter and the door will close
behind him. If the user wishes to leave the door closed he must leave
the LOCK function inserted on the 6-function selector. On the other
hand, if he wants to leave the door open he must turn the 6-function
selector to MAN and then immediately to AUTO. The door will unlock
the electric lock and it will then open and remain open either until the
power supply is restored or until the LOCK command is given once
again.
- In the event of power failure (with battery and electric lock with release
cable installed) the user will have to open the safety compartment and
unlock the electric lock. This will release the electric lock and enable the
user to operate the door as described above.
Option "2" will not activate the door in the absence of power and, if a
selector/switch is connected to the D/N (day/night) terminal and the
contact is closed (day), the lock will be released (whether it be an electric
lock with release cable or one with an automatic release). A single pulse
will cause the lock to release for the time set in Co-17.
- In the event of power failure (with battery and electric lock without
release cable installed) the user will have to turn an external key selector
activating the DAY command (emergency). This command will release
the electric lock so that the automatic door can be operated manually.
- In the event of power failure (with battery and electric lock with release
cable installed) the user will have to open the safety compartment and
unlock the electric lock. This will release the electric lock and enable to
CO-12
CO-13
CO-14
CO-15