Floor Mount
Wall Mount
Ceiling Mount
1.
Unpackage
A.
Remove unit from box. Check for any signs of concealed
damage, and that all optional equipment has been provid-
ed. Contact Air Innovations immediately if components
are missing or/if unit has been damaged in shipping.
B.
Shipment includes:
- One (1) fan-coil unit
- One (1) condensing unit
- One (1) remote interface controller with 50' control cable
- One (1) 7' clear plastic drain hose
2. Installing the Fan Coil
Wine Guardian split system fan coil units should be in-
stalled indoors located near the wine room. Provide a
three-foot clearance around the unit for installation and
future maintenance. The fan coil unit can be located ei-
ther above, or below the condensing unit in height. Keep
any height difference to a maximum of 15' (4.57meters).
Floor Mounting
•
Mount the Wine Guardian fan coil on a plywood sur-
face at least 12 inches above the floor to keep it
away from water. Allow adequate space for the rout-
ing and pitch of the external drain.
Wall Mounting
•
Provide adequate support on both ends of the unit
to accommodate the weight of the system. Construct
a structurally sound level platform, supported by
angle brackets fastened to the wall.
Ceiling Mounting
•
Construct a structurally sound, level platform to
place the unit on when hanging it from the ceiling
joists. The system is NOT designed to be suspended
from the top of the unit; it must be supported from
the bottom.
3.
Wiring Thermostat
A.
Unit is supplied with 50 feet (15 meters) of 6- wire,
cable with RJ14 type connection to the Remote
User Interface.
B.
Route the cable to the desired mounting location
within the room.
C. Locate Remote User Interface within the room mid-
point on a wall in an area with good airflow and away
from any windows or heat sources.
D. Remove back plate of controller and mark mounting
points at desired location.
3