Specifications
Smoke Detection
Heat Detection
Certification
Operating Modes
Wireless RF Modes
Alarm Sound Level
Typical Average Standby
Current:
Typical Alarm Current:
Typical Battery Life:
Battery Type:
Low Battery Threshold:
Low Battery Beep rate:
Low Battery Life:
Operating Temperature:
Operating Humidity:
Color:
Dimensions:
Transmitter Characteristics:
Nominal Center Frequency
Supervision Time
In order to continue improving the product, RISCO Group reserves the right to
change specifications and/or designs without prior notice.
Certifications:
EN14604:2005/AC:2008
1134-CPR-126
Ordering Information
Model
RWX34S
Photoelectric chamber
Dual-sensor with fixed temperature and rate-
of-rise
EN14604:2005/AC:2008
Smoke + Heat (OR logic)
Smoke only
Heat only
Selectable 1-way or 2-way
Exceeds 85dB at 3m (10')
0.02mA typical
100mA
Typically 3 years
Two CR123 3V lithium batteries
2.5 V
One beep every 30 seconds
30 days from warning signal
14°F - 104°F (-10°C to 40°C)
10% to 85% RH, no condensation or icing
White
Diameter: 4.25 in (108 mm)
Height: 2 in (53 mm)
Smoke & Heat Detector, 1 & 2 way 433.92 MHz
Smoke & Heat Detector, 1 & 2 way 868.65 MHz
15 min. for 868.65 MHz /
65 min. for 433.92 MHz
Description
Smoke & Heat Detector, 1 & 2 Way
9