Cord Sets and Receptacles
Use only high quality, well-insulated, grounded extension
cords with the generator's receptacles. Inspect extension
cords before each use.
Check the ratings of all extension cords before you use
them. Extension cord sets used should be rated for 125
Volts AC loads 20 Amps or greater. Check operator's
manuals of devices to be powered for the manufacturer's
recommendations.
Keep extension cords as short as possible to minimize
voltage drop.
WARNING Damaged or overloaded electrical cords
could overheat, arc, and burn resulting in death,
serious injury, and/or property damage.
• ONLY use cords rated for your loads.
• Follow all safeties on electrical cords.
• Inspect cord sets before each use.
120/240 Volt AC, 50 Amp Receptacle
Use a NEMA 14–50 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volt AC loads at 50 Amps to
the plug.
240 Volts AC
Frame Ground
Y (Hot)
120 Volts
AC
W (Neutral)
NEMA 14-50
This receptacle powers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 10,000 watts of power (10.0 kW) at
41.6 Amps for 240 Volts or two independent 120 Volt loads.
The outlet is protected by a 2 pole circuit breaker.
NOTICE Receptacles may be marked with rating value
greater than generator output capacity.
• NEVER attempt to power a device requiring more amperage than
generator or receptacle can supply.
• DO NOT overload the generator. See Don't Overload Generator.
X (Hot)
120 Volts
AC
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater). You can use the same 4-wire cord if you plan to run
a 120 Volt load.
4-Wire Cord Set
120V
Y (Hot)
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 7,200 watts of power (7.2 kW) at
30 Amps for 240 Volts or two independent 120 Volt loads at
30 Amps each. The outlet is protected by a 2 pole circuit
breaker.
120 Volt AC, 30 Amp Locking Receptacle
Use a NEMA L5–30 plug with this receptacle. Connect a
3–wire cord set rated for 125 Volt AC loads at 30 Amps to
the plug.
3-Wire Cord Set
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power at
30 Amps. The outlet is protected by a 2 pole circuit breaker.
240V
120V
W (Neutral)
X (Hot)
Ground (Green)
NEMA L5-30
Neutral
120V
Hot
Ground (Green)