Design of control wiring
• Connect each wire for controlling as shown below.
Central remote controller (Option)
U1
U3
(Open)
[Outdoor unit]
U1
U2
U3 U4
[Indoor unit]
U1
U2
PMV Kit
(Option)
Indoor control
P.C. board
CN82
• Wire specification, quantity, size of crossover wiring and remote controller wiring
Name
Control wiring
(indoor-indoor / indoor-outdoor / outdoor-
indoor control wiring, central control wiring)
Remote controller wiring
1. The crossover wiring and central control wiring use 2-core non-polarity transmission wires. Use 2-core shield
wires to prevent noise trouble. In this case, close (connect) the end of shield wires, and perform the functional
grounding for the end of the shield wires which are connected to both indoor and outdoor units.
For the shield wires which are connected between the central remote controller and the
outdoor unit, perform the functional grounding at only one end of central control wiring.
2. Use 2-core and non-polarity wire for remote controller. (A, B terminals)
Use 2-core and non-polarity wire for wiring of group control. (A, B terminals)
U2
U4
(Open)
To other
refrigerant
system
Relay connector
(At shipment from factory : No connection)
Control wiring between indoor and outdoor units
Control wiring between indoor units
Q'ty
2 cores
2 cores
Relay
U1
U2
connector
For control
For wiring of
wiring between
central control
indoor and
system
outdoor
Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor unit)
U1
U2
Up to 500m
Up to 1000m
1.25mm²
0.5 to 2.0mm²
24
U3
U4
Shield earth screw
Control wiring between indoor
and outdoor units
U1
U2
Size
1000 to 2000m
2.0mm²
—
—
Cable clamp
U1
U2
Specification
Shield wire
—