COURTESY LIGHT
This output has a normally-open clean contact relay which closes
for approx. 1 second at the start of an opening phase.
This switch may be used to activate a courtesy light timer (max.
load: 230V - 4 A).
The switch is on terminals K1 and K2.
BLINKER
The control unit provides for the use of a 230V - 40W or
120V - 40W blinker with built-in intermittence.
Connect the cables to terminals K9 and K10.
START INPUT
The START input is preset for connecting devices with the switch
normally open.
Function depends on the mode of operation set by means of dip-
switch 4.
Step mode
Subsequent Start command cause, in order:
g
g
g
opening
stop
closure
"Inversion" mode
Start during opening causes closure.
Start during closure causes opening.
Start with the gate open always results in closure; the only case
where this does not occur immediately is when automatic closure
is enabled and start while opening is not accepted: in this specific
case, start makes the pause time count start from zero, after
which the gate will be re-closed.
In both modes it is possible to disable the Start command during
gate opening by means of
dip-switch 3.
Connect the start input control device cables between terminals
L1 and L8 on the control unit.
PEDESTRIAN START
With the gate closed, the pedestrian start command causes partial
opening (approx. half way) of the gate leaf connected to motor 1.
Subsequent pedestrian start commands will function according to
step logic.
During a pedestrian cycle, the start command results in the
complete opening of both gate leaves.
Connect the pedestrian start input control device cables between
terminals L2 and L8 on the control unit.
stop
STOP
The STOP input is intended for devices with the switch normally
closed.
The STOP command causes the immediate stop of the gate.
A subsequent START command activates the gate in the opposite
direction of movement.
If the STOP command is given during opening or pause, then
there will be no subsequent automatic re-closure.
Connect the stop input control device cables between terminals
L3 and L8 on the control unit.
LIMIT SWITCH INPUTS
The control unit is configured for connecting a switch with switch
normally closed, which is opened when the gate reaches the
desired position.
Connect the limit switch cables as follows:
• Closing limit switch between terminals L6 and L8
• Opening limit switch between terminals L7 and L8
EXTERNAL ANTENNA
It is recommended the external antenna be used in order to
guarantee maximum radio capacity.
Connect the antenna hot pole to terminal A1 of the control unit
and the braiding to terminal A2