5.2
Technical data
Operating mode S1 (optional),
motor immersed
Oil-filled seal chamber
Oil quantity

5.3 Scope of supply

• Pump with 33 ft (10 m) connecting cable:
Mains voltage 230 V
• MTS 40/95...:
1~ version ready-wired (H07 RN-F 4 x 1,5 mm
with connector box incl. start-up/operating
capacitor
• MTS 40/95-120...:
3~ version with free cable end
(H07 RN-F 6 x 1 mm
• MTS 40/143-165...:
3~ version with free cable end
(H07 RN-F 7 x 2,5 mm
• MTS 40 E 95-120...:
3~ version with free cable end
(NSSHÖU 7 x 1,5 mm
• MTS 40 E 143-165...:
3~ version with free cable end
(NSSHÖU 7 x 2,5 mm
Mains voltage 460 V
• MTS 40/95-120...:
3~ version with free cable end
(H07 RN-F 6 x 1 mm
• MTS 40/143-165...:
3~ version with free cable end
(H07 RN-F 7 x 1,5 mm
• MTS 40 E 95-165...:
3~ version with free cable end
(NSSHÖU 7 x 1.5 mm
• Installation and Operating Instructions
5.4 Accessories
Accessories must be ordered separately.
• Switchgear for 1 or 2-pump operation
• external monitoring devices / tripping units
• level controller (level sensor / float switch)
• Accessories for transportable wet-well installa-
tion
• Accessories for stationary wet-well installation
see catalogue for detailed list.

6 Description and operation

6.1 Pump description

In order to ensure that the pump remains suffi-
ciently cool in continuous mode, the submersible
motor-driven pump must always be flooded with
the flow medium. The pump is driven by an
encased three-phase or single-phase motor
Installation and operating instructions Wilo-Drain MTS 40
MTS 40/...,
MTS 40 E...
Marcol 82 (medical white oil)
MTS 40/...
MTS 40 E...
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
S1: 200 hrs/year
S1: 2000 hrs/year
0.63 cups (150 ml)
0.97 cups (230 ml)
which is corrosion-resistant and impermeable to
pressurised water.
The pump housing and single-channel impeller
are made from grey cast iron. The flow medium is
sucked in on the underside of the pump through
the openings on the cutting device and is expelled
through the discharge side into the pipe.
The cutting device cuts up all dissectible constit-
uents so that they can be transported through the
single-channel impeller and the DN 40 pressure
pipe. The blades, cutters and counter-cutters are
made of hard metal. Constituents which cannot be
cut, such as stones or pieces of metal, damage the
cutting device and should therefore not be
allowed into the pump.
The motors are sealed from the flow medium by
means of a mechanical seal. Sealing from the oil
chamber is also by means of a mechanical seal on
types MTS 40 E..., where as a shaft seal is used on
types MTS 40/....
The oil chamber serves to cool and lubricate the
seals (see also 5.2).
CAUTION! Risk of leak!
If the mechanical seal is damaged, small quanti-
ties of oil may leak into the flow medium.
In addition to being connected by a foot bend
DN 40, the MTS 40 pumps can also be connected
to the pressure pipe using an elbow pipe (inner/
outer thread):
• Pressure pipe DN32 (1 ¼"):
MTS 40/95 - 120..., MTS 40 E 95 -120... using an
90° elbow pipe (inner/outer thread) 1 ¼".
• Pressure pipe DN40 (1 ½"):
MTS 40/95 - 165..., MTS 40 E 95 - 165... using an
90° elbow pipe (inner/outer thread) 1 ½" and
threaded flange with neck as per DIN 2566 with
inner thread 1 ½".
The motors are equipped with a winding protec-
tion contact (WSK) that automatically switches
off the motor if there is a threat of it overheating
and switches it back on again once it has cooled
down. On 3~motors, the winding protection con-
tact must be connected to the switchgear and
analysed there.
Within the motors of the MTS 40 E...(FM-
approved) pumps a leakage detector (DI) is
installed further away in the motor cavity which
indicates when water enters the motor.
English