Test Run - mundoclima MVD DC2 Manual De Instalación Y Usuario

Ocultar thumbs Ver también para MVD DC2:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SW7_1
SW7
Reserved
[
]
0
SW7_2
SW7
Unit with capacity less than 28kW
[
]
0
SW7
Unit with capacity equal or more than 28kW
[
]
1
J1
Auto restart function enabled
Auto restart function disabled
0/1 definition of each dial code switch:
means 0
Note
All DIP switches (including the capacity DIP switch) have been
configured before delivery. Only a professional maintenance
personnel should change these settings.
Improper DIP switch settings may cause condensation, noise, or
unexpected system malfunction.
The default DIP switch setting is based on the actual unit.
8.4 Error Codes and Definitions
Error
Content
code
E0
Mode conflict
E1
Communication error between indoor and outdoor units
E2
Indoor ambient temperature sensor (T1) error
E3
Indoor heat exchanger mid-point temperature sensor
(T2) error
E4
Indoor heat exchanger outlet temperature sensor
(T2B) error
E6
Fan error
E7
EEPROM error
Eb
Indoor EEV coil error
Ed
Outdoor unit error
EE
Water level error
FE
Indoor unit has not been assigned an address

9. Test Run

9.1 Things to Note Before Test Run
1) Indoor and outdoor units are properly installed;
2) Piping and wiring are correct;
3) No leakage from the refrigerant piping system;
4) Water discharge is smooth;
5) Insulation is complete;
6) Grounding line has been properly connected;
7) Piping length, and amount of refrigerant filled have been recorded;
8) The voltage of the power supply is the same as the rated voltage
of the air conditioner;
9) No obstacles at the air inlet and outlet of the indoor and outdoor
units;
10) Cut-off valves for the gas and liquid ends are opened;
11) Connect to the power supply to let the air conditioner warm up first.
9.2 Test Run
means 1
Use wired/remote controller to control and operate the air conditioner
in the cooling mode. Check the following items according to the
manual. If there is any fault, troubleshoot by referring to the section
"Air Conditioner Errors and Causes" in the manual.
9.2.1 Indoor unit
1) Wired/remote controller switch is operating normally;
2) Function keys of the wired/remote controller are operating normally;
3) Room temperature regulation is normal;
4) LED indicator is on;
5) Key for manual operation is normal;
6) Water discharge is normal;
7) No vibration and strange sounds during operation;
9.2.2 Outdoor unit
1) No vibration and strange sounds during operation;
2) If the wind, noise and condensation affect the neighbours;
3) Any refrigerant leakage.
Once the power is connected, when the unit is turned on or
started immediately after the unit is turned off, the air conditioner
has a protective function which delays the start of the
compressor by 3 minutes.
38