Combustion Adjustment; Ionisation Current - Riello 40 GS5 Instrucciones Para La Instalación, Uso Y Mantenimiento

Ocultar thumbs Ver también para 40 GS5:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC, the application of the burner on the boiler,
adjustment and testing must be carried out by observing the instruction manual of the boiler,
including verification of the CO and CO
the average temperature of the water in the boiler. It is advisable to set the burner according to
the type of gas used and following the indications of the table:
EN 676
Theoretical max. CO
GAS
0 % O
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
PROBE - ELECTRODE POSITIONING
IMPORTANT
Do not turn the starting electrode but leave it as shown in the drawing; if the starting electrode is put
near the ionization probe, the amplifier of the control box might be damaged.
Put the ceramic
near the diffuser disc
Probe
D5033

IONISATION CURRENT

The minimum current necessary for the
control box operation is 5 µA.
The burner normally supplies a higher cur-
rent value, so that no check is needed.
Should you want to measure the ionisation
current anyway, you must open the con-
nector (CN1) (see wiring diagram page 5) inserted in the red wire and insert a microammeter.
3288
concentration in the flue gases, their temperatures and
2
AIR EXCESS: max. output   1.2 – min. output   1.3
Setting CO
2
 = 1.2
2
9.7
9.5
11.6
11.4
Diffuser
Probe
%
2
 = 1.3
9.0
8.8
10.7
10.5
Ignition electrode
2
WARNING 2.5
D4625
Socket
of control-box
7
GB
NO
CO
mg/kWh
mg/kWh
 100
 170
 100
 170
 100
 230
 100
 230
Electrode
3.5 mm
Connector
_
+
x
Probe

Publicidad

Tabla de contenido
loading

Tabla de contenido