D.
Function
LOOP 1 commands opening and, at end of opening, closes if released (useful if a vehicle
23
reverses with consecutive loops).If disabled at disengagement of LOOP , no closure is
performed.
24
NOT USED
25
A.D.M.A.P function
If you enable this function, the safety devices operate according to French standards.
26
If you enable this function, during closure, the CLOSING SAFETY DEVICES stop movement
and, when disengaged, reverse movement, otherwise they reverse immediately.
27
NO EFFECT
PRELAMPEGGIO:
A 1
Used for adjusting - in sec steps - the duration of required pre-flashing, from a minimum
0
of
to a maximum of
TIMEOUT FOR REVERSING AT CLOSURE:
A2
If you enable this function, during closing, you can decide whether to reverse or stop the
movement when time out elapses (closing stroke limit not reached).
OPENING AT POWER UP:
A3
In case of a power cut, when power is restored, an opening operation can be commanded
by enabling this function (only if the automated system is not closed, FCC free).
TIME FOR ENABLING FAAC CITY PRESSURE SWITCH (J5):
This is the time after which the unit considers the signal originating from the pressure switch
A4
as the CLOSING TRAVEL-LIMIT.
Can be adjusted from
to show minutes and tenths of a second (separated by a dot), up to a maximum value
4,1
of
minutes.
DISABLING OF BOLLARD PRESSURE SWITCH AT START OF MOVEMENT:
A5
For a correct operation of the bollard, you have to disable the pressure switch check at
start of the upstroke movement (time: 0.4 seconds).
Y
Set this function to
BOLLARD SOLENOID VALVE POWER SUPPLY CHECK (terminals 22-23):
FAAC CITY K - J75K: solenoid valve output usually not supplied with power – supplied with
A6
power during downstroke.
FAAC CITY - J75 standard: standard: solenoid valve output usually supplied with power
– not supplied with power during downstroke.
A7
POLARITY OF OPENING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
A8
POLARITY OF CLOSING TRAVEL-LIMIT STOP:
Configuration of the travel-limit stop contact
FAAC CITY PRESSURE SWITCH ENABLE (J5):
A9
Detection of the PRESSURE SWITCH contact as safety device during the first upstroke phase
and as limit switch after activation time of FAAC CITY pressure switch (parameter
SAFETY ONLY PRESSURE SWITCH FOR BOLLARDS (terminals 7 - GND):
b0
Recognition of PHOTOCELL contact as a safety PRESSURE SWITCH.
(The contact is ignored at start of movement and at the end of the upstroke)
b 1
HOLD CLOSE / HOLD OPEN FUNCTION DELAY:
Delay of the activation of the HOLD CLOSE / HOLD OPEN function (see parameters b and
b4). The count starts when the involved limit switch has been reached.
If, at the end of the set time, the limit switch is involuntarily disengaged, the HOLD CLOSE /
HOLD OPEN function is activated.
00
= HOLD CLOSE / HOLD OPEN function activated immediately
01
99
to
= minutes of count before activation of HOLD CLOSE / HOLD OPEN
b2
DO NOT MODIFY
b3
HOLD CLOSE FUNCTION:
If the closing limit switch is involuntarily disengaged, the board commands automatically a
movement for sec. to restore the position; if the closing limit switch is not engaged during
this period of time, the automated system is activated max. for the operating time "t" see
nd PROGRAMMING LEVEL
b4
HOLD OPEN FUNCTION:
If the opening limit switch is involuntarily disengaged, the board comman-
ds automatically a movement for sec. to restore the position; if the ope-
ning limit switch is not engaged during this period of time, the automated sy-
stem is activated max. for the operating time "t" see nd PROGRAMMING LEVEL:
A3
(parameter
recommended on
10
seconds
0
59
to
sec. in second steps. Subsequently, the display changes
with bollards.
Y
if parameter
b3
Y
set on
):
4
Setting
Y
= closes if LOOP is free
no
= disables
/
Y
= enables
no
= disables
Y
= stops movement
and reverses when
disengaged.
no
= reverses immediately.
/
05
Y
= reversal
no
= block
Y
= opening
no
= stays idle
4.0
Y
= pressure switch not
active at thrust
no
= pressure switch always
active
Y
= for FAAC CITY K /J75K
no
= for FAAC CITY
standard and J75
Y
= NO polarity
no
= NC polarity
Y
= NO polarity
no
= NC polarity
Y
= Operation for FAAC CITY
no
A4
= Standard limit switch
):
operation
Y
= Operation of safety only
pressure switch
no
= Operation of standard
photocells
30
30
Y
= enables
no
= disables
Y
= enables
no
= disables