Fault Codes - Carrier HDB Manual De Instalación

Ocultar thumbs Ver también para HDB:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
HDB controller

Fault codes:

In the case of failure and with the unit ON, the red LED on the
board starts flashing according to the fault code: 0.5 seconds ON
and 0.5 seconds OFF followed by 5 seconds OFF.
The fault code table is shown below:
Fault Code
Description
2
Air temperature sensor
3
Changeover sensor
4
Cold Draft thermistor
5
Condensate pump error
6
Electric heater configuration error
7
EEprom error
8
Chilled Beam configuration error
GB - 6
Resettable
Yes
Yes
Yes
No
Yes
Yes
Yes

Publicidad

Tabla de contenido
loading

Tabla de contenido