MAINTENANCE AND SERVICING

Required Maintenance

The HM700 humidifier has been designed to require very little
maintenance. Regular maintenance consists of checking the
humidifier to ensure it is in good condition, replacing the
cylinder when the software advises that the cylinder is spent
and cleaning out the drain valve whenever the cylinder is
replaced.

CYLINDER SPENT FAULT

When the cylinder is spent the HM700 will stop operating and
the yellow LED will flash in a repeating pattern of 4 flashes.
See Table 8 on page 22 for more information on other flash
sequences. At this time the cylinder must be replaced.
The steam cylinder is disposable and must be replaced at end
of cylinder life. Cylinder life is dependent on water supply
conditions and humidifier usage.
HIGH WATER SENSOR PIN HAS
A PLASTIC COLLAR AROUND IT.
CONNECT ORANGE HIGH WATER
SENSOR WIRE HERE.
ELECTRODE INTERNAL
MOUNTING POINT.
NOTE: Honeywell recommends keeping a replacement
REPLACEMENT CYLINDER
The label on the existing cylinder identifies the cylinder type in
its top left corner. When ordering a cylinder always quote the
three or five digit model number on the label, the humidifier's
serial number and the humidifiers voltage. Serial number and
voltage are located on the specification label on the left side of
the humidifier.
STEAM OUTLET
SECURE STEAM HOSE TO
OUTLET WITH HOSE CLAMP.
Fig. 22. HM700 cylinder (HM700ACYL2).
17
CAUTION
Failure to replace the cylinder at the end of
cylinder life will result in improper operation and
may result in damage to the humidifier. Honeywell
is not responsible for any damages resulting from,
or attributed to, the failure to replace a spent
cylinder (see Manufacturer's Warranty).
cylinder in stock throughout the humidification
season. This will prevent possible downtime
when the humidifier reports cylinder end of life.
ELECTRODE PIN
CONNECT COLOR CODED CYLINDER
PLUGS TO PIN WITH CORRESPONDING
COLOR LABEL. THE SPRING LOADED
PLUG SHOULD FIT SNUGLY ON THE PIN.
REPLACE IF LOOSE OR ANY SIGNS OF
DAMAGE.
LABEL
IDENTIFIES CYLINDER INFORMATION.
ALSO INCLUDES SAFETY INFORMATION
AND CONTACTS.
HM700A1000
M35704
33-00118EFS—03

Publicidad

Tabla de contenido
loading

Tabla de contenido