Steam Distributor
The HM700 requires a steam distributor installed in the
supply-side of ductwork. The HM700 can distribute steam into
a ventilation duct using the distributor shown in Table 5.
Part Number
Stainless Steel Distribution
HM700ADISTKIT
Remote Mount Kit
W
1/3W
2/3W
MIN. W=8 (203)
1
2
3
Table 5. Steam distributor.
Description
H
1/3W
1/3W
1/3W
Fig. 6.
1 TURN
+45˚
–45˚
M35756
Fig. 7.
The steam distributor should be installed as close as possible
to the humidifier. Short steam distribution lines minimize
condensate loss and the possibility of generating
backpressure in the steam distribution line.
Includes a steam distributor, 5 ft. insulated steam hose, condensate
hose, and installation hardware.
Fig. 8. Distributor installed horizontally
M35755
Fig. 9. Distributor installed horizontally in a vertical duct.
Rotate the distributor 45º so that steam is discharged
toward the center of duct, in the direction of the air flow.
AIR FLOW
Fig. 10. Distributor installed vertically in a horizontal duct.
This configuration is not recommended.
7