Energi Savr Node

Out-of-Box Functionality

This section describes the default functionality that the unit will present
when first installed.
Inputs (Occ, Daylight, IR, and Switch)
• Input group 1: controls zone 1.
• Input group 2: controls zone 2.
• Input group 3: controls zone 3.
• Input group 4: controls zone 4.
Occupancy Sensors (Occ)
• Corresponding zones will turn on when the occupancy sensor is in the
occupied state (closed) and off when in the unoccupied state (open).
Daylight Sensors (Daylight)
• Corresponding zones will turn on when light sensed by daylight sensor
falls below the factory preset level.
• Corresponding zones will turn off when light sensed by daylight sensor
rises above the factory preset level.
• QSN-4T16-S and QSN-4T16-S-347: Corresponding zone light levels will
raise or lower when light sensed by daylight sensor falls or rises based
on a factory default setting.
Keypads and IR Receivers (IR)
• See IR Receiver literature for compatible transmitters.
• Corresponding zones respond to On, Off, and Scene commands from
compatible IR controls.
• QSN-4T16-S and QSN-4T16-S-347: Corresponding zones respond to
Raise and Lower commands from compatible IR controls.
Sample application: Out-of-Box Functionality
(requires no commissioning)
Zone 3
Daylight
Sensor
Room 3
Room 1
Daylight
Sensor
English
for 0 –10 V / Energi Savr Node
TM
Wired to
Input
Group 3
Energi Savr
Node
unit
TM
Occupancy
Sensor
Zone 1
Occupancy
Sensor
Wired to
Input
Group 1
Español
with Softswitch
TM
IEC PELV / NEC
Class 2 Dry-Contact Closure (Switch)
®
• Maintained closure or open toggles corresponding zone(s) between
preset and off.
Contact Closure Input (CCI)
• Momentary closure from a normally-open (NO) dry-contact closure
device will result in all zones being turned off.
Emergency Contact Closure Input (Emerg)
• If the Emergency input is open, the ESN unit will enter Emergency Mode,
which will turn on all loads and disable local zone control and control
from sensors and QS devices.
• When the Emergency input is closed or jumpered, ESN unit zones will
return to the settings or levels they were at prior to entering Emergency
Mode.
seeTouch
QS Wallstations
®
• All seeTouch
QS lighting wallstations are Scene keypads by default.
®
• QSN-4S16-S and QSN-4S16-S-347: Scenes 1–16 will turn on all the
lights.
• QSN-4T16-S and QSN-4T16-S-347: Scenes 1–16 will dim lights to the
preset levels indicated in the table below:
Scene # Light Level: All Zones
1, 5–16 100%
2
75%
3
50%
4
25%
• Scene Off will turn all the lights off.
Wired to
Input
Group 4
Occupancy
Sensor
Occupancy
Zone 2
Sensor
Wired to
Input
Group 2
Français
Português
| Installation Guide
®
Zone 4
Daylight
Sensor
Room 4
Room 2
Daylight
Sensor
Lutron
| 13
®