Step-by-Step Installation Instructions
Step 3: Feed-Through Load Wiring
4 Circuits, Single Feed (QSN-4T16-S, QSN-4T16-S-347)
The ESN unit control power must be 120 –277 V~. Zone switching can be 120 –277 V~ or 347 V~ (for 347 V~ models only). Use the following
instructions to wire line voltage loads to the ESN unit.
Load Wiring
• Two (2) 14 to 12 AWG (2.5 to 4.0 mm
• Strip length: 3/8 in (8.5 mm)
• Torque: 7 in-lb (0.79 N•m)
Distribution Panel A
Hot
Neutral
Ground
120–347 V~
Distribution Panel B
Hot
Neutral
Ground
Ground
120–277 V~
Hot
Neutral
* For 347 V~
models only.
0–10 V Wiring (QSN-4T16-S and QSN-4T16-S-347)
• 20 to 12 AWG (0.5 to 4.0 mm
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
m)
• Connect only IEC PELV / NEC
®
PELV / NEC
Class 2 circuits to 0–10 V zones 1–4.
®
• 0–10 V zones 1–4 are not isolated from each other.
8 | Lutron
®
for 0 –10 V / Energi Savr Node
TM
(continued)
(continued)
2
)
Ground
Lug
Neutral Wires
Zone Switching:
120–277 V~; 347 V~*
0–10 V Zones:
(QSN-4T16-S,
QSN-4T16-S-347)
2
)
Class 2 circuits or connect only non-IEC
with Softswitch
TM
WARNING! Danger of Shock. May result in serious injury or death.
DO NOT WIRE WHEN LIVE! Switch off power to all power feeds via
circuit breaker before wiring or servicing the ESN unit.
The ESN unit is a feed-through device. This means that each switched
output needs the Line and Load wires. THERE IS NO INTERNAL
CONNECTION BETWEEN THE CONTROL POWER TO THE UNIT AND
THE SWITCHED OUTPUTS.
Zone 1
Zone 2
Zone 3
Zone 4
1A
1B
2A
2B
3A
3B
4A
4B
Zone 1
Zone 2
Zone 3
Zone 4
Zone 1
Zone 2
Zone 3
Zone 4
+
+
+
+
+
+
+
+
0–10 V Outputs
• Negative (–) terminals are not internally connected to each other; both
positive (+) and negative (–) connections must be made.
• Follow all national and local codes for separation requirements.
• Each 0–10 V zone corresponds to a switched zone. Any 0–10 V load
must be connected to both the 0–10 V terminals and the corresponding
switched zone.
| Installation Guide
®
Load
Load
Load
Load
0–10 V Wiring
(QSN-4T16-S,
QSN-4T16-S-347)