9
Cause of Faults, Remedial Action
► Outlet pressure rises above set value
Seal is dirty or cone seal leaking.
Remedial action:
Clean taper or replace if necessary.
► Outlet pressure falls below zero consumption
Diaphragms or piston seal leaking, or spring cover or flange screws not screwed
tight enough.
Remedial action:
Replace diaphragms or piston seal, or retighten spring cover or flange screws (see
point 5.6).