2.2.13 Holiday Mode
At the function setting page, select "Holiday mode" and set it to "On" or "Off".
NOTE
This function can be activated only when the unit has been turned off, otherwise a prompt dialog box will pop up, saying "Please
turn off the system first!".
When "Holiday mode" has been activated, the operation mode will automatically switch to "Heat". "Mode" setting and "On/Off"
operation through the controller will be unavailable.
When "Holiday mode" has been activated, the controller will automatically deactivate the "Weekly timer" and "Preset mode", "Clock
timer" and "Temp.timer".
Under the "Holiday mode", when the unit is under the control of room temperature, the set point (room temperature for heating)
should be set to 10°C; when it is under the control of leaving water temperature, the set point (leaving water temperature for heating)
should be 30°C.
When this function has been activated, "Floor debug", "Emergen.mode", "Disinfection", "Manual defrost", "Preset mode", "Weekly
timer", "Clock timer" and "Temp.timer" cannot be activated at the same time, meanwhile a window will pop up, saying "Please
disable the holiday mode!".
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.
2.2.14 Preset Mode (daily timer)
At the function setting page, select "Preset mode" and go to the corresponding setting page.
This function allows to set up to four periods per day.
At the time period setting page, each time period can be set to "Valid" or "Invalid".
On "Mode" the operating mode can be set between "Cooling", "Heating" or "DHW".
The temperature of the cold / hot water at the outlet can be set on "WOT-Heat.
On " Start timer " / " End timer " the start and end time can be set.
After that, by touching the "Save" icon, all settings will be saved.
NOTE
"Preset Mode" is a repetitive daily timer.
The "DHW" mode can be selected only if "DHW tank" is set to "Active". For a possible subsequent deactivation of the tank, the control
switches "ACS" with "Heating".
"Start timer" should be earlier than "End timer", otherwise a dialog will pop up, saying "time setting wrong".
The setting for "Preset mode" will works until it has been canceled manually.
When "Start timer" is reached, the unit will perform the preset mode. In this case, mode and temperature setting are still allowed but
will not be saved to the preset mode. When "End timer" is reached, the unit will perform OFF operation.
The priority of the timers is as follows: Time bands (high) - Timer - Preset mode - Weekly timer (low)
This function will be memorized upon power failure (see 2.6.1 On/Off memory).
The default value is Off.
< Save
< Save
43