2.5.10 Floor Debug (for radiant panels)
At the commissioning parameter setting page, by touching "Floor debug", the control panel will access to the corresponding setting page.
The function activates a preheating cycle, which can be repeated over time, at a defined water temperature and for a defined time. If the cycle is
repeated then the water temperature is increased by the ∆T value.
At the setting page can be set:
No.
Displayed Name
1
Floor debug
2
Segments
3
Period 1 temp
4
Segment time
5
∆T of segment
When this setting is finished, by pressing "Start" this setting will be saved and start working, and by pressing "Stop" the function will halt.
NOTE
This function can be activated only when the unit is turned off. When it is done with the unit keeping "On", a window will pop up, saying
"Please turn off the system first!".
When this function has been activated, "On/Off" operation will be deactivated. By pressing On/Off, a window will pop up, saying
"Please disable the Floor debug!".
When "Floor debug" has been activated, "Weekly timer", "Clock Timer", "Temp timer" and "Preset mode" will be deactivated.
"Emergen. mode", Disinfection", "Holiday mode", "Manual defrost", "Forced mode" and "Refri. recovery" cannot be activated at the
same time with "Floor debug". If doing so, a window will pop up, saying "Please disable the Floor debug!".
Upon power failure, "Floor debug" will back to "Off" and the runtime will be zeroed.
When "Floor debug" has been activated, "T-floor debug" and "Debug time" can be viewed (on Visual / Parameters see 2.4.2)
When "Floor debug" has been activated and works normally, the corresponding icon will be displayed at the
upper side of the menu page.
Before activating "Floor debug", make sure "Segment time" of each segment is not zero. If so, a window will pop up, saying "Segment
time wrong!" In this case, "Floor debug" is allowed to be activated only when "Segment time" has changed.
The setting is memorized and re-proposed in case of power failure (see 2.6.1 On/Off memory).
The default value is Off.

2.5.11 Manual Defrost

At the commissioning parameter setting page, by touching "Manual defrost", the control panel will access to the corresponding setting page.
This function forces a Defrost cycle.
NOTE
This setting can be set only when the unit has turned off. If the function is active, the On / Off key is disabled.
Defrosting will quit when the defrosting temperature goes to 20°C ("T Defrost" on Visual / Parameters see 2.4.2) or the defrosting
duration is equal to 10 minutes.
When "Manual defrost" has been activated, the corresponding icon will be displayed at the upper side of the menu page.
This setting will not be memorized upon power failure.
The default value is Off.
Full Name
Floor debug switch
Quantity of segments
Temperature of the first segment
Duration of each segment
Temperature difference of each segment
52
Range
Default
On/Off
Off
1÷10
1
25÷35°C
25°C
12÷72 hours
0
2÷10°C
5°C
ELECTA-ECO
Accuracy
/
1
1°C
12 hours
1°C