Configure the system - Input and output configuration
In the example of pic. 4, the input and output are set as
show below:
Par. 110.0 : 22 (Proportional Valve, Command Open)
Par. 110.1 : 23 (Proportional Valve, Command Close)
Par. 110.2 : 26 (Pool three way valve)
Par. 110.3 : 0
Par. 110.4 : 0
Par. 110.5 : 1 (Water Pump)
Par. 111.0 : 0
Par. 111.1 : 0
Par. 111.2 : 0

Wiring Connection Diagram

Connector Pin
50
51
52
53
54
55
N
Neutral Reference
*: Refer to variable table and output value table to configure the desired function.
Connector Pin
23
41
42
20-21
40
*: Refer to variable table and input value table to configure the desired function.
Description
Output 1*
Max 2A 230Vac 50Hz
Output 2*
Max 2A 230Vac 50Hz
Output 3*
Max 2A 230Vac 50Hz
Output 4*
Max 2A 230Vac 50Hz
Output 5*
Max 2A 230Vac 50Hz
Output 6*
Max 2A 230Vac 50Hz
Max 4A 230Vac 50Hz
Description
Input 1*
Dry Contact
Input 2*
Dry Contact
Input 3*
Dry Contact
Input 7 *
Dry Contact
Common
Digital GND
Par. 111.3 : 0
Par. 111.4 : 0
Par. 111.5 : 0
Par. 111.6 : 10 (Flow Switch)
Par. 112.3 : 1 (Temperature Sensor Water Entering in
exchanger)
Par. 112.4 : 1 (Temperature Sensor Leaving Water to Pool)
Par. 112.6 : 1 (Temperature Sensor Pool Water)
OUTPUT
Type
Available for devices connected. Reference for all
230Vac Outputs
INPUT
Type
Reference for all dry contact input, except input 7
Note
Note