Installation

Configure the system - Variable table

Refer to Comfort Module and User Interface installation
manual to configure the network.
The Pool Kit works in the same way of a 2 zones Kit, but
use different logics dedicated to swimming pool heating/
cooling. The Par. 124 must be set to 2 to work as Pool Kit.
NOTE: Only one Pool Kit is admitted in the network.
Nr.
Name
Par.
1
Pool Setpoint (Point A in pic. 5)
2
Pool Temperature
4
User Mode
5
Failed Addresses
6
Fault Codes
11
User Config
12
Antifreeze Setpoint
15
Pool Hysteresis
Adjust Heating Climatic Curve
16
(Ref. X in pic. 6)
Adjust Cooling Climatic Curve
17
(Ref. Y in pic. 6)
19
Temperatures
31
Flow Switch Status
After the addressing of all the devices of the network,
moving on the parameter of Variable Table to configure all
the relevant settings.
The description of the parameters of Variable Table
dedicated to the Pool Kits, are shown below. All the other
parameters have no changes.
Pool kit can work in heating or cooling mode, pool mode is
independent from the main system mode.
Description
LEVEL 0
Actual pool setpoint (°C)
Actual pool temperature (°C)
Actual mode operation
0. Off
1. N.A.
2. Cooling
3. Heating
Addresses of devices in fail. Scrolled every 1 second
Fault codes scrolled every 1 second
LEVEL 1 and 2
Use Days button to select the subparameter
Pool antifreeze option
0 : Disable
1 : Enable
Allow user to change setpoint/schedule settings for
the zone.
0. Allowed
1. Not Allowed
Water Pump (if mapped) behaviour
0. Water pump does not stop when pool setpoint is
reached
1. Water pump stops when pool setpoint is reached
Pool antifreeze setpoint (°C)
Hysteresis on Pool Temperature (°C)
Delta temperature applied to the maximum
temperature of heating climatic curve (°C)
Delta temperature applied to the minimum
temperature of cooling climatic curve (°C)
Use Days button to select the subparameter
If Pool Board, show the temperatures of:
Water from Comfort Module entering in pool
exchanger (°C)
Leaving temperature to the pool (°C)
Sanitary Water (°C)
Outdoor air, read by the Comfort
Module sensor (°C)
LEVEL 3
Reading
Displays the Flow Switch status:
0.Water not flowing
1. Water Flowing
RANGE
MIN
MAX
DEFAULT
12
30
25
-
-
-
0
3
0
-
-
-
-
-
-
0
0
0
6
12
6
0.1
2
0.5
-5
5
0
-5
5
0
-
-
-
-
-
-
2
80HMA - 9002