Installation
Configure the system - Variable table
Nr.
Name
Par.
32
Pressure Switch Status
38
Pool Water Set Point
51
Heating Climatic Curve nr.
Heating Climatic Curve Point A
52
(see pic. 6)
Heating Climatic Curve Point B
53
(see pic. 6)
Heating Climatic Curve Point D
54
(see pic. 6)
Heating Climatic Curve Point C
55
(see pic. 6)
56
Cooling Climatic Curve nr. (see pic. 5B)
Cooling Climatic Curve Point B
57
(see pic. 6)
Cooling Climatic Curve Point A
58
(see pic. 6)
Cooling Climatic Curve Point D
59
(see pic. 6)
Cooling Climatic Curve Point C
60
(see pic. 6)
Delta Pool Setpoint Priority 0.5
75
(Ref. B, pic. 5)
Delta Pool Setpoint Priority 1
76
(Ref. C pic. 5)
104
Output test
110
Output Setup
3
80HMA - 9002
Description
Displays the Pressure Switch status:
0. No pressure
1. Pressure
Water set point requested by the pool kit (°C)
Climatic curve
Selection of Heat climatic curve:
0. User define climatic curve
1-6. Pre-set climatic curve (not designed for pool)
User define heating climatic curve:
minimum ambient outdoor temperature (°C)
User define heating climatic curve:
maximum ambient outdoor temperature (°C)
User define heating climatic curve:
water setpoint at Par. 53 value (°C)
User define heating climatic curve:
water setpoint at Par. 52 value (°C)
Selection of Cool climatic curve:
0. User define climatic curve
1-2. Pre-set climatic curve (not designed for pool)
User define cooling climatic curve: maximum ambient
outdoor temperature (°C)
User define cooling climatic curve: minimim ambient
outdoor temperature (°C)
User define cooling climatic curve: water setpoint at
Par. 57 value (°C)
User define cooling climatic curve: water setpoint at
Par. 58 value (°C)
Priority
Value of Delta from Pool Setpoint to have Priority 0.5 in
the Priority Chart (fig. 5) (°C)
Value of Delta from Pool Setpoint to have Priority 1 in
the Priority Chart (fig. 5) (°C)
System control
Force ON the output
0.No output forced
1.Output 1
2.Output 2
3.Output 3
4.Output 4
5.Output 5
6.Output 6
Use Days button to select the sub-parameters.
Output values.
Use HOLD to quickly switch between plus and minus
PIN 4 - Output 1
Select output code
PIN 31 - Output 2
Select output code
PIN 16 - Output 3
Select output code
PIN 17 - Output 4
Select output code
PIN 6 - Output 5
Select output code
PIN 8 - Output 6
Select output code
RANGE
MIN
MAX DEFAULT
-
-
-
-
-
0
6
0
-20
15
10
10
50
30
20
60
35
20
80
25
0
2
0
24
46
40
0
30
22
4
20
12
4
20
18
1
5
3
1
5
2
0
6
0
-35
35
0