GAS PIPELINE FILTER AND GAS SOLENOID VALVE FILTER
Check periodically the cleaning of the filters.
On reinstalling them be careful not to damage the gaskets and check for gas leaks.
PRESSURE STABILISER
Rotate the screw shown in fig. 23 to adjust the gas pressure.
Tighten the screw to increase the pressure, loosen the screw to
decrease it.
The adjustable screw shall never be at the end of the stroke as,
should this happen, the pressure stabiliser will no longer be able
to work.
The maximum efficiency of the burner will not be achieved if there
is no adequate pressure in the gas valve.
GAS FILTER
To clean the gas filter close the gas shut-off valve on the pipeline;
remove the filter cover, take off the cartridge and clean it care-
fully, if possible by compressed air.
When putting the cover back in place be careful not to pinch the
OR ring and check for gas leaks.
FIG. 25
When installing a stabiliser with inset filter it is recommen-
ded to assemble it at a convenient height from the floor to
make the cleaning of the filter set in the lower part easier.
20
GB
FIG. 23
FIG. 24