Cross Frame Routing Tray Installation - Leviton HDF3168 Guia Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Using the cable grommet sizing tool, determine the appropriate quantity of rubber rings to remove
from each cylinder. To ensure a snug fit around each cable only remove as much material as
necessary.
4. With the Clamp assembly mounted to the Mesh panel, determine the cable grommet mounting
location (approximately 1inch behind the shrink tube breakout) and mark the cable(s).
5. Remove the clamp assembly from the Mesh, place all cables in the target grommet, center the
grommet in the grommet clamp and secure the grommet clamp with the wing nut and bolt.
6. Insert the loaded Clamp assembly to the desired Mesh mounting location. The assembly is
secure when the release pin engages the receiving hole.
Tip:
For best results position the cut in the cable grommet against the metal wall of the grommet
clamp. This will minimize over-compression or deformation of the grommet.
6.

Cross Frame Routing Tray Installation

Install a Leviton HDF 3168 Cross Frame Routing Kit by following these steps:
1. Facing the front of the Frame, install the left routing tray first (Figure 26). With the tray in the
collapsed position, place in the desired location and expand the tray until the tabs can be
positioned in the left routing slot (ex. Figure 29) and over the center frame body respectively.
2. Facing the front of the Frame, install the right routing tray first (Figure 27).With the tray in the
collapsed position, place in the desired location and expand the tray until the tabs can be
positioned in the right slot (ex. Figure 29) and over the center frame body respectively.
3. Install the Front Routing Tray (Figure 28) directly in front of the Right Routing tray using the
provided #12/24 screws to the appropriate holes in the rack rails.
4. Tighten all expansion nuts prior to use.
Warning:
DO NOT OVERTIGHTEN
Figure 26
3. MOUNT THE
CENTER ROUTING
TRAY LAST
DI-000-F3168-20B
Leviton HDF3168 Fiber Distribution System User Guide
Figure 27
1. MOUNT THE
LEFT ROUTING
TRAY FIRST.
Figure 29
Figure 28
2. MOUNT THE
RIGHT ROUTING
TRAY NEXT
32

Publicidad