16
UK
ON
DIP 6
OFF
ON
DIP 7
OFF
ON
DIP 8
OFF
ON
DIP 9
OFF
ON
DIP 10
OFF
DEFAULT SETTINGS
• DIP 1 and DIP 2 both OFF:
• DIP 3 OFF:
• DIP 4 OFF:
• DIP 5 OFF:
• DIP 6 ON:
• DIP 7 OFF:
• DIP 8 OFF:
• DIP 9 OFF:
• DIP 10 ON:
USE OF THE LIMIT SWITCHES
When using the deceleration function, the board operates
in two different modes depending on whether it is the
opening or the closing phase.
• During opening, deceleration will start when the limit
switch reaches the beginning of the shaped cam.
The motion will stop when the limit switch meets the end
of the shaped part.
• During closing, deceleration will start when the limit
switch reaches the beginning of the shaped cam.
When the limit switch reaches the end of the shaped
part, a full-power stroke is generated to perfectly close
the door.
AUTOMATIC CLOSING
DECELERATION
FAST CLOSING
LED POWER SUPPLY
Step-by-step with stop
Pre-flashing disabled
Safety device test disabled
Opening photocell disabled
Automatic closing enabled
Deceleration disabled
Fast closing disabled
Uninfluential
LEDs powered
Enables automatic closing after the pause time adjustable with the
trimmer TR2 PAUSE between 2 and 215 seconds.
Disables automatic closing.
Enables deceleration during both opening and closing when the respective
limit switch is intercepted.
The deceleration speed is adjusted with the trimmer TR6 SLOW.
This function utilises 2 suitably shaped cams (for positioning see 2).
Disables the deceleration function.
Requires 2 suitably shaped cams (for positioning see 2).
Reduces the pause time to 3 seconds after intervention of one of the
photocells.
Disables the fast closing function.
Not used.
Not used.
Supplies the LEDs (which will come on depending on the respective con-
tact). After proper installation, the LED power supply can be deactivated
to save energy.
Disables the warning LED power supply.
Motor
off
OPENING CAM
BSC24
Deceleration
start
CLOSING CAM
Start of
final stroke
Deceleration
at full power
start
2