Step-by-Step Installation Instructions

Set the Operating Current

Follow these instructions to configure the DIP
switch. The following illustration shows an
enlarged view of the DIP and rotary switches.
Warning: Power MUST remain OFF before
setting or changing the DIP or rotary
switches. Changing these switches with
the power ON will not be recognized by
the system and is dangerous due to the
risk of electric shock.
1.
Turn OFF power.
2.
Use a non-conductive object to adjust the
DIP switch settings:
Switch Position 1:
For a Line to Line connection
(200-250V), set the DIP switch to
DOWN.
For a Line to Neutral connection
(greater than 250V), set the DIP
switch to UP.
Switch Position 2:
DIP Switch Position 2 should
always be set to UP.
18
Wiring/
Connection
Line to Neutral
(greater than
250V)
Line to Line
(200-250V)
3.
Set the rotary switch for the appropriate
current setting supported by your circuit
breaker. Typical circuit breaker ratings are:
15A, 20A, 25A, 30A, 35A, 40A, 45A, and
50A.
Use a small flathead screwdriver to adjust
the rotary switch to the appropriate circuit
breaker capability setting. The
corresponding rotary switch settings for
the typical circuit breakers are shown in
the following table: