WITCHING ON FROM BATTERY
¾ Make sure that the battery rack switch/fuse is closed.
¾ Hold down "Battery Start" (See "Communications View – point 3") for about 5 seconds. The UPS becomes active and
the display comes on.
¾ Press
to access the System on menu. When confirmation is requested, select "YES" and press

confirm. All the LEDs around the display light up for about 1 second and the buzzer starts to emit a beep about every
7 seconds.
N.B. if the sequence which has just been described is not performed within 1 minute, the UPS switches off automatically
so that the batteries are not run down unnecessarily.
S
ETTING THE RATED BATTERY CAPACITY
After installing one or more BATTERY BOXES, it is necessary to configure the UPS in order to set the exact value of the
overall rated capacity.
To perform this operation, use the dedicated configuration software.
Battery maintenance
The system automatically checks battery efficiency every 24 hours and provides an alarm when it finds efficiency which
is much lower than the level calculated on the basis of the memorised capacity value. Battery life is linked to the
operating temperature and the number of charging and discharging cycles performed.
The capacity is not constant. It increases after a few charging and discharging cycles. It remains constant for a few
hundred cycles and then decreases permanently.
Preventive battery maintenance includes the following:
keeping the operating temperature at between 20 and 25°C;
x
during the first month of use, performing two or three charging and discharging cycles;
x
after the first month, performing the operation every six months;
x
As the batteries are a source of energy, opening the battery switch does not eliminate the voltage inside the
x
batteries. DO NOT ATTEMPT TO ACCESS THE INSIDE OF THE BATTERY RACK.
DANGEROUS VOLTAGE IS ALWAYS PRESENT AROUND THE BATTERIES. If in doubt about whether the
x
batteries are faulty, contact the assistance service.
Any replacement of the batteries must be performed by qualified personnel. In order to dispose of the
replaced components, it is compulsory to send them to an agency specialised in disposal through
recycling. The batteries are classified as "toxic waste" by law.
S
WITCHING OFF THE
From the main menu, select "OFF" and press
press
. At this point, the load is no longer powered. In order to switch the UPS completely, it is necessary to open

SWIN and the battery rack switch/fuse. Wait for a few seconds until the display goes off.
N.B. during extended periods of inactivity, it is good practice to switch the UPS off by opening the input and
output isolating switches. Finally, once the UPS is off, open the battery fuse holders.