AS400
PORT
PIN #
1
15
2
REMOTE ON
8
REMOTE OFF
7
4,5,12
BATTERY LOW
6,13,14
9,10
3,11
N.B.: The figure shows the contact present inside the UPS, capable of carrying a maximum current of between 0.5A
and 42Vdc.
The position of the contacts shown in the figure is with no alarm or signal present.
(1)
The output can be programmed using the specific configuration software.
The function shown is the default function (factory configuration).
IV333 Rev.000 SIEL S.p.A.
Data di emissione: 2011-09-28
NAME
TYPE
15V
POWER
GND
POWER
INPUT #1
INPUT #2
REMOTE
INPUT #3
BYPASS
OUTPUT #1
BATTERY
OUTPUT #2
WORKING
LOCK
OUTPUT #3
BYPASS
OUTPUT #4
AS400 PORT
Isolated auxiliary power supply +15V±5% 80mA max
Earth to which the isolated auxiliary power supply (15V) and
the remote commands (Remote ON, Remote BYPASS,
Remote OFF) refer
Connecting pin 2 to pin 15 for at least 3 seconds causes the
Connecting pin 8 to pin 15 causes the UPS to switch off
Connecting pin 7 to pin 15 causes the load feed to switch
from the inverter to the bypass. For as long as the
connection remains, the UPS continues to operate from the
bypass even if the input mains voltage fails. If the jumper is
removed in the presence of mains voltage, the UPS
resumes operation from the inverter. If the jumper is
removed when no mains power is present, the UPS begins
to operate from the battery again
Signals that the battery are about to run out when the 5/12
contact is closed
Signals that the UPS is operating from the battery when the
6/14 contact is closed
When the contact is closed, this signals that the UPS is in
When the contact is closed, this signals that the load is
powered through the bypass
FUNCTION
UPS to switch on
instantly
(1)
(1)
(1)
lock mode
(1)