Operation.FOrced.CIrculation.SYstems - Sime FORCED 200 Manual Del Usaurio

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Install.a.pressure.reducer,.where.required,.for.the.inlet.domestic.hot.water..Install.a.calibrated.safety.valve.according.to.that.
indicated.on.the.data.plate.applied.to.the.storage.tank.and,.in.standard.cases,.install.a.6.BAR.safety.valve..
Install.an.8.bar.safety.valve.on.the.cold.water.inlet.of.the.boiler.in.order.to.protect.the.product.from.excessively.high.pressure..
Place.a.water.pressure.regulator.at.the.mains.water.inlet,.which.must.be.calibrated.at.a.maximum.level.of.4.5.bar,.in.the.event.
the.boiler.is.installed.in.an.area.where.the.mains.water.pressure.is.too.high.(on.average.more.than.6.5.bar)..
If.the.mains.water.is.too.hard.(20.°F),.install.a.purifying.device,.correctly.calibrated,.in.front.of.the.boiler.
Before.commissioning,.we.recommend.making.sure.that.the.flanges.and.the.connections.of.the.removable.coils.are.fastened.
correctly..
The.storage.tank.temperature.must.not.exceed.95.°C.to.prevent.damage.to.the.inner.coating.
We.recommend.cleaning.inside.the.boiler.every.12.months..Check.the.magnesium.sacrificial.anodes.every.12.months.to.prevent.
corrosion..Inspect.where.water.is.particularly.aggressive.
OPERATION FORCED CIRCULATION SYSTEMS
Forced.circulation.solar.systems.are.used.to.produce.domestic.hot.water..They.constitute.an.ecological.proposal.and.ef-
ficient.energy.solution.that.combines.high.results,.autonomy,.design,.easy.installation.and.money.savings;.moreover,.they.
reduce.the.consumption.cost.of.the.traditional.energy.sources.considerably.
The.system.automations.control.the.temperature.difference.between.the.solar.collectors.and.the.boiler;.in.addition,.they.
provide.the.relative.commands.to.ensure.the.continuous.supply.of.hot.water.according.to.the.circuit.regulations.
The.differential.thermostat.is.programmed.electrically.to.control.the.thermal.differential.and.is.supplied.with.interface.
keys.and.a.screen.to.display.the.parameters.and.messages..Moreover,.it.comes.with:
-.Closed.circuit.antifreeze.protection.system.
-.Overheating.closed.circuit.protection.system.
When.the.temperature.of.the.solar.collector.exceeds.that.of.the.boiler.by.6-10.°C,.the.solar.system.circulator.activates.
(thermal.differential.implementation)..The.circulator.stops.the.operation.when.the.temperature.drops.to.20.°C.(hyster-
esis)..In.the.event.of.system.inertia,.a.command.can.be.sent.to.an.auxiliary.energy.source.(electric.or.central.heating).
All the components required for the connection are included in the packaging.
All the components are suitable for the mixture of water and glycol.
FR
ENG
IT
ES
41

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Forced 300Forced 40085018128501813

Tabla de contenido