Lenze TML Instrucciones Para El Servicio página 16

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Commissioning
Code
No.
Name
CE1
Configuration -
Digital input E1
CE2
Configuration -
Digital input E2
Configuration -
CE3
Digital input/output E3
C08
Configuration - Relay
output (terminals K14
and K12
14
Possible Settings
Lenze Selection
1
1
Activate fixed setpoint 1 (JOG1)
2
Activate fixed setpoint 2 (JOG2)
3
DC braking (DCB)
4
Direction of rotation
5
Quick stop
6
CW rotation
2
7
CCW rotation
8
UP (setpoint ramp-up)
9
DOWN (setpoint ramp-down)
10 TRIP set
11 TRIP reset
12 Accel/decel 2
3
1...12 (same as above)
13...19 (reserved)
20 Ready
21 Fault
22 Motor is running
23 Motor is running - CW rotation
24 Motor is running - CCW rotation
25 Output frequency = 0Hz
26 Frequency setpoint reached
27 Frequency threshold (C17) exceeded
28 Current limit (motor or generator mode)
reached
29 Dynamic braking
Note
A
CFG
fault will occur under the following conditions:
• E1...E3 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections
made for CE2 and CE3 will be ignored.
1
Relay is energized if
0
Ready
1
Fault
2
Motor is running
3
Motor is running - CW rotation
4
Motor is running - CCW rotation
5
Output frequency = 0Hz
6
Frequency setpoint reached
7
Frequency threshold (C17) exceeded
8
Current limit (motor or generator mode)
reached
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
IMPORTANT
Activate JOG3: Both terminals = HIGH
see also C36
LOW = CW rotation
HIGH = CCW rotation
Controlled deceleration to standstill,
active LOW; Set decel rate in C13
or c03
CW rotation = LOW and CCW rotation
= LOW: Quick stop; Open-circuit
protected
UP = LOW and DOWN = LOW: Quick
stop; Use momentary NC contacts
EEr
Active LOW, triggers
(motor
coasts to standstill)
NOTE: NC thermal contact from the
motor can be used to trigger this input
see also c70
see c01 and c03
• 1...12 configures terminal E3 as
an input.
• 20...29 configures terminal E3 as a
current-sourcing (PNP) output rated
12 VDC / 50 mA

Publicidad

Tabla de contenido
loading

Tabla de contenido