Troubleshooting And Fault Elimination - Lenze TML Instrucciones Para El Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Troubleshooting and fault elimination

5
Troubleshooting and fault elimination
Status
Present output frequency
e.g.
50.0
Stop (outputs U, V, W inhibited)
OFF
Inhibit (outputs U, V, W inhibited)
1nh
Output frequency = 0 Hz
stP
(outputs U, V, W inhibited)
Flying restart attempt
FSt
DC-injection brake active
br
Motor calibration is in process
CAL
Current limit reached
CL,FCL
Undervoltage on DC bus
LU
Overvoltage on DC bus during
dEC
deceleration (warning)
No access to code
nEd
Remote keypad is active
rC
Error
A/D converter error
Ad
Identification fault
bF
cF
CF
Data on EPM not valid
GF
Automatic start inhibited
LC
EPM error
F1
Digital inputs not
CFG
uniquely assigned
Dynamic braking fault
dF
External error
EEr
Internal fault
FC5,
F2
F0
...
(1) The drive can only be restarted if the error message has been reset; see c70
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
Cause
Trouble free operation
LOW signal at terminal 28
Controller is set up for remote
keypad (see C01)
Quick stop activated through digital
input
c42 = 2, 3
DC-injection brake activated
• via digital input
• automatically
c48 = 1 and terminal 28 = HIGH
Controllable overload
Mains voltage too low
Excessively short deceleration time
(C13, c03)
Can only be changed when the control-
ler is in
OFF
or
1nh
Attempt to use buttons on front of
controller
Cause
C93 value stored on EPM does not
match controller model
Data not valid for controller
Data error
OEM data not valid
c42 = 0, 2
EPM missing or defective
E1...E3 assigned with the same digital
signals
Either just "UP" or "DOWN" used
Dynamic braking resistors are
overheating
Digital input "TRIP set" is active
Remedy
Set terminal 28 to HIGH
Start the controller via the remote
keypad
Deactivate Quick stop
Deactivate DC-injection brake
• digital input = LOW
• automatically after holding time c06
has expired
Only perform the motor calibration
when C14 = 4...7
Automatically (see C22)
Check mains voltage
Automatically if overvoltage
< 1 s,
, if overvoltage > 1 s
OU
Set terminal 28 to LOW
Buttons on front of controller are dis-
abled when remote keypad is active
(1)
Remedy
Please contact Lenze
• Use EPM providing valid data
• Load Lenze setting
LOW-HIGH signal change at terminal 28
Power down and replace EPM
Each digital signal can only be used
once
Assign the missing digital signal to a
second terminal
Increase deceleration time
Remove external error
Please contact Lenze
21

Publicidad

Tabla de contenido
loading

Tabla de contenido