General safety information
}
Danger!
Improper use of the module and the standard device may cause serious injury
and property damage.
Observe the chapters "Safety instructions" and "Residual hazards" contained
in the instructions for the standard device.
}
Danger!
When the request for the safety function is deactivated, the drive can restart
automatically. The behaviour can be set via the parameter "Restart behaviour"
(C15300/1/2).
In the case of an automatic restart, you must provide external measures which
ensure that the drive only restarts after an acknowledgement (EN 60204).
(
Stop!
Before mounting/dismounting, switch off the supply voltage to prevent
electronic modules from damage.
)
Note!
The entry in code C00214 must correspond to the type of the plugged−on
safety module. Otherwise, the controller will report the following error:
"Safety module: Incompatible to setting in C00214".
EDK94AYAE DE/EN/FR/ES/IT 3.1
Safety instructions
General safety information
l
1
25