Display
Parameter
Value
Immediate closure / Timer: This function enables you to activate immediate closure or automation shut-down with
the OPEN/CLOSE command. The function can be activated only when combined with function logics with automatic
re-closure, Automatic logic, Automatic step-by-step logic, or Condo.
Immediate closure activated: with the automated system open in pause mode, an impulse of
0
the OPEN/CLOSE command causes the automated system to close immediately without waiting
for the pause time to elapse.
P
Timer function activated: If you activate this function, with the automated system open in pause
state, at every OPEN/CLOSE command, the control unit restarts the pause time count. If the
1
command is maintained active, the control unit stops the pause time count and the automated
system remains idle. The control unit resumes the pause time count only when the OPEN/CLOSE
command is released.
Soft start: This function enables a softer start of the automated system.
0
Soft start function disabled
r
1
Soft start function enabled
Operation of safety devices: This parameter enables you to select the intervention method of the safety devices
connected to the control unit.
0
Safety devices active only during closure of the automated system
y
1
Safety devices active during the closure and opening of the automated system
Assistance request: This function allows you to set the number of cycles to be run before maintenance begins. For
information about the operation of this function, see the next paragraph.
0
Assistance request disabled
1
Assistance request after 10,000 cycles
2
Assistance request after 20,000 cycles
3
Assistance request after 30,000 cycles
4
Assistance request after 40,000 cycles
U
5
Assistance request after 50,000 cycles
6
Assistance request after 60,000 cycles
7
Assistance request after 70,000 cycles
8
Assistance request after 80,000 cycles
9
Assistance request after 90,000 cycles
Cycle counter: The number of cycles, in thousands, performed by the automated system is displayed. For example, if
"15" is shown, this means that the automated system has performed 15,000 cycles. For more detailed information, see
the next paragraph.
00
Indicates the number of cycles performed by the automated system
The indicated conditions are the control unit's default. Make a note of the adjustments carried out in order
to restore them if the control unit is replaced.
You can access and modify the operation parameters only when the automated system is closed in rest
position - the display must indicate value "– –".
Whenever you access display / modification of the operating parameters, at the next OPEN impulse, the control
unit runs a programming procedure, recalculating the opening and closing time. The automated system does
not perform the slow-downs during the first opening.
0.. ASSISTANCE REQUEST
This function allows you to set the number of cycles to be run before a technical assistance job. When the number of
set cycles is reached, this is signalled by about 5 seconds flashing, at the end of every closure manoeuvre and the
control unit's display indicates value "AS". The resetting of the number of cycles must be done manually.
This function signals but does not prevent normal operation of the automated system.
The screen after parameter "U" shows the number of cycles in thousands, e.g., if you read "05"this means that the
automated system has performed 5,000 cycles. The maximum number of cycles the control unit can count is 99,000
- when this value is reached, the count stops and must be manually reset.
10.1.1. r
esetting the nuMber oF cycles
This is the procedure for resetting the number of cycles:
1.
Press and hold down push-button P1 until the first parameter "A" appears on the display.
2.
Scroll all the operating parameters until the number of performed cycles is shown.
3.
Simultaneously press push-buttons P1 and P2 for about 10 seconds.
Description
25