The Parisienne - ref. 124 03 01 - 124 05 01
X
- Forbidden
1
- Flue duct
2
- Stainless funnel-shaped register
3
- Encasing of the flue connector : 40 mm
2.3. Chimney
The chimney must comply with Current Building
Regulations. If in doubt, consult your Dealer or local
Building Inspector.
-
Chimney to be built / New flue :
The chimney must comply with Current Building
Regulations. If in doubt, consult your Dealer or local
Building Inspector.
-
The flue must be in good condition and must provide
sufficient draught (refer to technical details p. 3 ).
-
The flue must be clean. It should be swept to remove
soot and dislodge tar deposits.
-
The flue must be well insulated. If the flue inner wall
surfaces are cold, a good thermal draw is impossible
causing condensation problems (tar formation etc.) to
occur.
-
The flue must be watertight.
-
The chimney must have a constant cross section.
-
The flue must not be shared with other appliances.
-
The chimney must be at least 4.5 m (15 ft high).
-
In case of a flat roof or when the roof gradient is lower
than 15°, the stack must be 1,2 m (4 feet) high at least.
-
The capping must not restrain the draught.
-
If the chimney draught is excessive or irregular, a
draught stabilizer (barometric damper) must be
installed to the connector pipe it must be visible and
accessible.
Technical manual "286"
1
6
7
4
- Funnel-shaped fire cement
5
- Flange
6
- The flange does not extend beyond the encasing
7
- Soot door
Figure 3 - Connections to flue
Flue non-existent :
-
The chimney must comply with Current Building
Regulations. If in doubt, consult your Dealer or local
Building Inspector.
-
The flue must not be supported by the stove.
-
Consult a chimney specialist for advice on suitable
flue systems for solid fuel appliances.
-
It must be distant from any combustible material
(walls, cross members)
-
It must permit an easy sweeping.
2.4. Hearth
The stove must stand on a fireproof hearth and must be
situated at least 300 mm (12 inches) from any
combustible material.
The positioning of the stove and the size of the hearth
are governed by building regulations for Class 1
appliances.
These building regulations state that the hearth must
extend in front of the stove by at least 300 mm
(12 inches) and to the sides of the stove by at least 150
mm (6 inches) If in doubt as to the positioning of the
stove expert advice should be sought either from the
supplier or the local building inspector.
1
4
5
Installation instructions
2
3
7
5