Error message "Incompatible sensor"
Important (Notice)
When commissioning the device, make sure that the transmitter is assigned to the sensor
correctly. It is not possible to operate a flowmeter sensor of the 300 series with a transmitter of
the 500 series.
If the transmitter is operated with a flowmeter sensor of another series, the following message
appears on the transmitter display:
Boiler 9
Q
Σ+
Σ-
Diagnostics
Operator Page 1
Operator Page 2
Back
Back
CI/FEX300/FEX500-X1
0.00 l/min
1403.09 m3
591.74 m3
Sensor
-Operator Menu-
Select
Sensor
-- F248.036--
Incompatible sns
Tx+snr are not
the same series
Exit
In the process display, a flow of zero flow is indicated, no
flow measurement is performed.
1. Use
to switch to the information level.
2. Use
or
3. Use
to confirm your selection.
When attempting to commission a mixed installation, the
shown error message appears.
The device cannot measure.
The indicated value for the current flowrate is zero flow.
The current output assumes its pre-configured state (Iout
for alarm).
Make sure that the flowmeter sensor and the transmitter
are from the same series.
(e.g., flowmeter sensor ProcessMaster 300, transmitter
ProcessMaster 300)
FEX300, FEX500
Commissioning