Tabla de contenido

Publicidad

POWER WIRING

Refer to the input voltage rating marked on the fixture, and then wire according to
the diagram and table below.
POWER
GROUND
Low voltage fixture (120–277 V ± 15%)
Supply voltage
120 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
208 VAC, 3 Ф derived from 3 Ф,
208/120 V panel
240 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
240 VAC, 1 Ф derived from 3 Ф,
240/120 V panel, B phase wild
277 VAC, 1 Ф derived from 3 Ф,
480/277 V panel
10
L1
L1 (BLACK IN US/CA/MX; BROWN
OUTSIDE US/CA/MX)
L2
L2 (WHITE IN US/CA/MX; BLUE
OUTSIDE US/CA/MX)
GROUND (GREEN IN US/CA/MX; GREEN
W/YELLOW OUTSIDE US/CA/MX)
Fixture's L1 (black)
connects to
H (black)
L1 (black), L2 (red), or L3
(blue)
L1 (black)
L1 (black), L2 (orange), or
L3 (blue)
L1 (brown), L2 (orange), or
L3 (yellow)
FIXTURE
Fixture's L2 (white)
connects to
N (white)
L2 (red), L3 (blue), or L1
(black)
L2 (red)
L2 (orange), L3 (blue), or
L1 (black)
N (white)