External Voltage Supply - Lenze Ethernet POWERLINK Instrucciones Para El Montaje

Ocultar thumbs Ver también para Ethernet POWERLINK:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6
Electrical installation

External voltage supply

External voltage supply
)
Note!
Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.
The external voltage supply of the communication module is required if the Ethernet
POWERLINK communication is to be continued in case the supply of the standard device
fails.
Supply the communication module via the 2−pole plug connector (X210) by means of a
separate supply voltage.
Designation
+
Terminal data
Field
Electrical connection
Possible connections
Starting torque
Stripping length
42
Description
External voltage supply
V = 24 V DC (20.4 V ... 28.8 V)
I = 140 mA
Reference potential for external voltage supply
Values
2−pole plug connector with screw connection
Rigid: 1.5 mm
Flexible:
Without wire end ferrule
1.5 mm
With wire end ferrule, without plastic sleeve
1.5 mm
With wire end ferrule, with plastic sleeve
1.5 mm
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
6 mm
l
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)
2
(AWG 16)
EDK94AYCEP DE/EN/FR/ES/IT 4.0

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

E94aycep

Tabla de contenido