3
Installation instructions
3.1 Fitting
Field bus node CPX−FB13 is mounted in a manifold sub−
base of the CPX terminal.
1
Screws, tightening
torque 0.9...1.1 Nm
2
Field bus node
CPX−FB13
3
Contact rails
4
Manifold sub−base
Dismantling
Remove the screws and carefully lift up the field bus
S
node.
Fitting
1. Check the seal and sealing surfaces and refit the sub−
base.
2. Place the screws so that the self−cutting threads are
used. Tighten the screws by hand in diagonally oppo
site sequence. Tightening torque 0.9...1.1 Nm.
Festo CPX−FB13 0503a English
1
2
3
4
15