Descargar Imprimir esta página

Nova-12Rm; Description - Optimus NOVA-500 Manual De Instalación Y Funcionamiento

Publicidad

Idiomas disponibles

Idiomas disponibles

3. NOVA‐12RM 
3.1. DESCRIPTION 
NOVA‐12RM is used for remote control of the system. It includes 12 programmable keys with the 
following functions: 
 
-
Zone/group selection for paging. 
-
Activation of Internal messages, individual or list as BGM. 
-
Activation of Audio input broadcasting to output zones as BGM. 
 
It has balanced audio transmission and supports 24V phantom power, no power source is required. 
 
It is connected to the system with straight CAT5 cable (minimum UTP, recommended FTP). Up to 32 
units can be installed, and maximum cable distance 600 m. 
1. Busy status indicator. 
Green: the equipment is busy, please wait; Off: normal state, equipment can be used for calling
or control functions. 
2. Microphone. 
Microphone with ring LED. It is activated during paging. 
3. Key status indicators.  
Light in green: key function in working condition. Flashing: key selected. OFF: not selected. 
4. Programable keys. 
 
NOVA Version 1.0
NOVA
Voice Evacuation System
Page 10 of 34
 
 

Hide quick links:

Publicidad

Capítulos

loading

Este manual también es adecuado para:

Nova-500sNova-12rm