4. SYSTEM CONNECTION AND CONFIGURATION 
4.1. SYSTEM CONNECTION EXAMPLE 
4.2. POWER SUPPLY CONNECTION 
NOVA‐500  and  NOVA‐500S  can  be  supplied  with  AC  power  110~250V  50/60Hz 
and  at  with  DC  power  24V.  In  case  of  using  low  AC  voltage  (110~125V)  please 
replace the 5 A fuse for 10 A one.   
In case of 24V input, the voltage range is 20‐27.5V and the power source should 
be of at least 32 A.   
Remote  microphones  are  powered  through  the  bus  from  NOVA‐500  and  
NOVA‐500S. 
4.3. BUS CONNECTION 
Use CAT5 (minimum UTP, recommended FTP) straight cable to connect the NOVA‐500 to extension 
controller  NOVA‐500S  or  other  system  units.  System  max  capacity  is  19*  NOVA‐500S  and  32* 
NOVA‐12RM units and maximum communication distance is up to 600 meters.  
 
System can support loop or star connection. Loop is recommended for redundant connection.  
 
Note: no failure is detected when loop is opened in a single point.