Descargar Imprimir esta página

Danfoss Optyma AK-RC 111 Guia De Instalacion página 3

Ocultar thumbs Ver también para Optyma AK-RC 111:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
Function
View set point
Change set point
Change menu "User level"
Return
Change menu "Installer level"
Return
List of level 1 variables (user level)
Variables
Meaning
r0
Temperature difference compared to main SETPOINT
d0
Defrost interval (hours)
If d0 = 0 cyclical defrosts Off
d2
End-of-defrost setpoint.
Defrost is not executed if the temperature read by the defrost sensor is greater than
d2. (If the sensor is faulty defrosting is timed)
d3
Max defrost duration (minutes)
d7
Drip duration (minutes)
At the end of defrost the compressor and fans remain at standstill for time d7, the
defrost LED on the front panel flashes.
F5
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for a time F5 after dripping. This time begins at the
end of dripping. If no dripping has been set the fan pause starts directly at the end of
defrost.
A1
Minimum temperature alarm
Allows user to define a minimum temperature for the room being refrigerated. Below
value A1 an alarm trips: the alarm LED flashes, displayed temperature flashes and the
buzzer sounds to indicate the problem.
A2
Maximum temperature alarm
Allows user to define a maximum temperature for the room being refrigerated. Above
value A2 an alarm trips: the alarm LED flashes, displayed temperature flashes and the
buzzer sounds to indicate the problem.
tEu
Evaporator sensor temperature display (displays nothing if dE =1)
List of level 2 variables (installer level)
Variables
Meaning
F3
Fan status with compressor off
F4
Fan pause during defrost
F6
Evaporator fans activation for air recirculation.
The fans activate for a time defined by F7 if they have not started working for the F6
time. If activation time coincides with the defrosting time, end of defrosting is awaited.
F7
Evaporator fans duration for air recirculation.
Fans working time for F6
dE
Sensor presence
If the evaporator sensor is disabled defrosts are carried out cyclically with period d0:
defrosting ends when an external device trips and closes the remote defrost contact or
when time d3 expires.
d1
Defrost type, cycle inversion (hot gas) or with heater elements
dPo
Defrost at Power On
dSE
Smart defrost
dSt
Smart defrost Setpoint (if dSE=1)
The counting of the time between the defrost is incremented only if the compressor is
ON and the evaporator temperature is less than dSt.
© Danfoss | DCS (vt) | 2019.08
Press
+
/
+
(3 seconds)
+
(3 seconds)
+
+
(3 seconds)
+
(3 seconds)
ENGLISH
Evaporator temperature
0 = Fans run continuously
1 = Fans only run when compressor is working
2 = Fans disabled
0 = Fans run during defrost
1 = Fans do not run during defrost
0 – 240 min
0 = (function not activated)
0 – 240 sec
0 = evaporator sensor present
1 = no evaporator sensor
0 = heating element
1 = hot gas
2 = heater with temperature control
0 = disabled
1 = defrost at power-on (if possible)
0 = disabled
1 = enabled
-30 – 30 °C
Value
0.2 – 10 °C
0 – 24 hours
-35 – 45 °C
1 – 240 min
0 – 10 min
0 – 10 min
-45 – (A2-1) °C
(A1+1) – 99 °C
Value
AN30923034432301-000101 | 3
Default
2 °C
4 hours
15 °C
25 min
0 min
0 min
-45 °C
99 °C
read only
Default
1
1
0 min
10 sec
0
0
0
0
1 °C

Publicidad

loading

Este manual también es adecuado para:

Optyma ak-rc 113