Descargar Imprimir esta página

Danfoss Optyma AK-RC 111 Guia De Instalacion página 5

Ocultar thumbs Ver también para Optyma AK-RC 111:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
Variables
Meaning
In1
INP-1 input setting
In2
INP-2 input setting
bEE
Buzzer enable
mOd
Thermostat functioning mode
P1
Password type of protection
(active when PA is not equal 0)
PA
Password
(see P1 for the type of protection)
reL
Release software
Troubleshooting
Alarm code Possible cause
E0
Cold room temperature sensor not working properly
E1
Defrost sensor not working properly (in this case defrosts will last time d3)
E2
Eeprom alarm
An EEPROM memory alarm has been detected
(All outputs except the alarm one are deactivated)
E8
Man in cold room alarm
Ec
Compressor protection tripped
(e.g. thermal protection or max pressure switch)
(All outputs except the alarm one – where applicable – are deactivated)
Ed
Open door Alarm. When the door is opened and after tdo time, it's setted back the
normal functioning giving door open alarm (Ed)
E9
Cell light alarm.
The light of the cell has been on for a time greater than tdo.
EH
Maximum temperature alarm.
The temperature inside the cold room has exceeded the max. temperature alarm
setting (see variables A2, user programming level)
EL
Minimum temperature alarm.
The temperature inside the cold room has exceeded the min. temperature alarm
setting (see variables A1, user programming level)
© Danfoss | DCS (vt) | 2019.08
Value
8 = Night mode digital input (energy saving,
N.O.)
7 = Stop defrosting remotely (N.O.) (reads rising
edge of impulse)
6 = Start defrosting remotely (N.O.) (reads rising
edge of impulse)
5 = Stand-by remotely (N.O.) (In order to indicate
Stand-By mode, the display shows 'In5'
alternating with the current view)
4 = Pump-down pressure switch (N.O.)
3 = Man-in-room alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man-in-room alarm (N.C.)
-4 = Pump-down pressure switch (N.C.)
-5 = Stand-by remotely (N.C.) (In order to
indicate Stand-By mode, the display shows
'In5' alternating with the current view)
-6 = Start defrosting remotely (N.C.) (reads falling
edge of impulse)
-7 = Stop defrosting remotely (N.C.) (reads falling
edge of impulse)
-8 = Night mode digital input (energy saving,
N.C.)
( like In1 )
0 = disabled
1 = enabled
0 = Cold function
1 = Hot function
(in this mode defrosting and fan disable Fst
are excluded)
0 = only display set point
1 = display set point, AUX, light access
2 = access in programming not permitted
3 = access in second level programming not
permitted
0...999
0 = not active
indicates software version
Solution
• Check that cold room temperature sensor is working properly
• If the problem persists replace the sensor
• Check that defrost sensor is working properly
• If the problems persists replace the sensor
• Switch unit off and back on
• Reset the alarm input inside the cold room
• Check that compressor is working properly
• Check compressor absorption
• If the problem persists contact the technical assistance service
• Check door switch status
• Check door switch connections
• If the problem persists contact the technical assistance service
• Turn off the light
• Check that the compressor is working properly.
• Sensor not reading temperature properly or compressor start/stop
control not working.
• Check that the compressor is working properly.
• Sensor not reading temperature properly or compressor start/stop
control not working.
AN30923034432301-000101 | 5
Default
2
1
1
0
3
0
read only

Publicidad

loading

Este manual también es adecuado para:

Optyma ak-rc 113