BTL7-A/E501-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S140/KA_ _/FA_ _
Micropulse Transducer - Rod Style
9
Adjust with the calibration device
NOTICE!
Interference in function
Adjustment while the system is running may result in
malfunctions.
► Stop the system before performing adjustment.
Initial situation:
–
Transducer with magnet within measuring range
Activate adjusting
► Press
for at least 4 s.
Set start point
► Bring magnet to the new start point.
► Press
for at least 2 s.
⇒ The new start point is set with the last valid start
value.
Adjust start value
► The start value can be changed using
The gradient of the curve changes (see page 18).
► End calibration procedure: Briefly press
simultaneously (< 1 s).
⇒ Set position value is saved.
For setting the end point, adjusting the end value,
and exiting adjustment, see page 21.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
1) Briefly press button: Current value is increased or
decreased by approx. 1 mV or 1 mA.
If a button is held down longer than 1 s, the step
interval is increased.
20
english
2
> 4 s
1
> 2 s
1
1
and
.
1)
2
2
and
< 1 s
1
LED legend:
LED not on
LED green
LED display
Displayed values (example)
LED1 LED2 At 0 to 10 V
5.39 V
5.39 V
1.04 V
0.00 V
0.00 V
2.00 V
2.00 V
2
LED 1 and LED 2 flashing green-red in alternation
LED 1 and LED 2 flashing red-red in alternation
At 4 to 20 mA
9.15 mA
9.15 mA
4.82 mA
4.00 mA
4.00 mA
7.20 mA
7.20 mA