Electrical Connections To The Electric Pump Pwm 203 - 202 - 201; Table 3: Current Absorption And Thermal Magnetic Circuit Breaker Sizing For Maximum Power; Figure 5: Pump Connection Pwm 203 - 202 - 201 - DAB PUMPS PWM 203 Instrucciones De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 234
The rated voltage of the electric pump must be the same as the supply voltage of the inverter.
The rated frequency of the electric pump can be set via the display according to the specifications on the manufacturer's dataplate.
For example, the inverter can also be powered at 50 [Hz] with control of an electric pump at 60 [Hz] - nominal (provided that the
pump is declared as compatible for this frequency).
For special applications, pumps are also available with frequency up to 200 [Hz].
The utility connected to the inverter must not absorb current in excess of the maximum values specified in Table 1.
Check the dataplates and type of motor connection (star or delta) used to ensure compliance with the above conditions.
2.2.1.4
Electrical connections to the electric pump PWM 203 – 202 – 201
Models PWM 203 – 202 – 201 require motor configuration for a three-phase voltage of 230V. This is normally obtained by a delta
configuration of the motor. See Figure 5.
Incorrect connection of the earthing line, to a terminal other than the earth terminal can cause irremediable
damage to the equipment.
Incorrect connection of the power line on the output load terminals can cause irremediable damage to the
equipment.
Current absorption and thermal magnetic circuit breaker sizing for maximum power
Supply voltage [V]
Max. motor current absorption [A]
Max. inverter current absorption [A]
Rated current of thermal magnetic circuit breaker [A]
Supply voltage [ 3 x V]
Max. motor current absorption [A]
Max. inverter current absorption [A
Rated current of thermal magnetic circuit breaker [A]
Supply voltage [ 3 x V]
Max. motor current absorption [A]
Max. inverter current absorption [A
Rated current of thermal magnetic circuit breaker [A]

Table 3: Current absorption and thermal magnetic circuit breaker sizing for maximum power

ENGLISH
Figure 5: Pump connection PWM 203 - 202 – 201
74
PWM 203
PWM 202
230 V
11,0
25,0
32
PWM 407
PWM 405
380
480
380
15,0
11,5
11,0
20,5
16,5
16
25
20
20
PWM 420
PWM 415
380
480
380
41,0
32,5
31,0
55,0
44,0
42,0
63
50
50
PWM 201
230 V
230 V
9,0
6,5
18,7
12,0
20
16
PWM 404
480
380
8,7
9,0
12,0
12,5
16
16
PWM 410
480
380
24,5
22,0
33,0
29,5
40
32
480
7,2
10,0
16
480
17,5
23,5
25

Publicidad

Tabla de contenido
loading

Tabla de contenido