WARNING
!
It is absolutely forbidden to connect the unit
to the public mains and/or another electrical
power source .
Areas for which access by non-authorized person-
nel is forbidden are:
- the control panel (at the front) - the endothermic
motor discharge.
GENERATION IN AC (ALTERNATING CURRENT)
Make certain of the efficiency of the ground con-
nection (12).
- See page M25.
Move the accelerator lever (16) and reach the en-
gine maximum speed.
Position the G.F.I. switch to ON.
+ Tension is now immediately available to the c.c
sockets.
Connect the electric devices to be powered to the
AC sockets, using suitable plugs and cables in
prime condition.
+ Verify that the electrical characteristics of the
tension/frequency/power device are compatible
with those of the generator.
Low frequency and/or voltage can damage some
electrical devices irreparably.
Verify that the ground terminal for the plug is pro-
perly grounded and connected to the electrical
appliance/tool to be powered.
+ For double insulation devices with the symbol
, the plug's ground terminal must not be
grounded.
Using the generator
THERMOPROTECTION
The generator is protected against overloads by the
thermoprotection (59B).
When current is exceeded, the protection feature
intervenes to cut off tension to the AC sockets.
+ Notes: the intervention of the thermoprotection
feature is not instantaneous, but reacts according
to an overcurrent/time characteristic, whereby the
greater the overcurrent the quicker the intervention.
In case of intervention by the protection feature,
verify that the total power for the loads connected
does not exceed the declared rating; decrease if
necessary. Disconnect the loads and wait a few
minutes to allow the thermo-protection to cool down.
ON
PUSH TO
RESET
If the protection should intervene once more, repla-
ce it with another one with matching intervention
current specifications and/or contact the Service
Department.
+ Note: do not forcibly press the central pole on
the thermoprotection to inhibit its intervention, as
this could damage the unit's alternator irreparably.
GE 4000 LDS/GS
OFF
Reset the protection feature
by pressing the central pole,
then connect the load once
again.