Measurement Over The Broken Delta - Woodward HighPROTEC MCDLV4 Manual Del Usuario

Ocultar thumbs Ver también para HighPROTEC MCDLV4:
Tabla de contenido

Publicidad

2 Hardware

2.6.4.2 Measurement Over the Broken Delta

2.6.4.2
Measurement Over the Broken Delta
Elemento de Ejemplo
20000 V
L1
L2
L3
V̲ L 12
V̲ L 23
V̲ L 31
After the voltage inputs have been connected correctly the residual voltage is measured
with the following setting:
• »VG[x] . Fuente VG« = «medido»
The broken delta is usually realized such that the RMS value of the residual voltage in
case of a 1p ground fault equals the RMS value of the phase-to-phase voltage.
Quotient / Scaling Based on Vn
All voltage thresholds of the voltage protection modules are set in units of the nominal
voltage Vn, that is dependent on the settings »VT . TVT sec« and »VT . TVT pri«.
Example: For the voltage transformer data shown in the diagram above (secondary
voltage = 100 V / 3), we have:
• »VG[x] . VG>« = 1.0⋅Vn = 100 V
Residual Voltage in Case of a 1p Ground (Earth) Fault
• VG med = 1.0⋅Vn
Example: For the voltage transformer data shown in the diagram above (secondary
voltage = 100 V / 3), the result is:
• VG med = 1.0⋅Vn = 100 V
136
100 V
3
3
V̲ L 1
V̲ L 2
V̲ L 3
Par. cam./VT
Nombre
Valor
VT pri
20000
VT sec
100
VT con
Fase a masa
TVT pri
20000
TVT sec
100
Sinc V
L12
VG̲ '
MCDLV4
Unidad
V
V
V
V
X?.
1
2
3
4
5
6
da [e]
7
dn [n]
8
MCDLV4-3.7-ES-MAN
VL1/VL12
VL2/VL23
VL3/VL31
VG

Publicidad

Tabla de contenido
loading

Tabla de contenido