8.17 Electrical actuators - TD_SA_1033 / Actuadores eléctricos - TD_SA_1033
•
Operating voltage: 24V AC
•
Power Consumption: 17VA
•
Control signal: 0-10V DC or 4-20mA
•
Operating temperature: –15°C to 50°C (23°F to 131°F)
•
Media temperature: -10°C to 140°C (14°F to 284°F)
•
Spring-return to closed position during failure (fail-safe)
•
Weight: 3.4 kg (7.5 lbs)
•
Minimum service space recommended: 100mm (4in) sides, and 200mm (8in) above.
•
The actuator can be installed in any position between vertical (Best) and horizontal.
•
Mounting location: NEMA 1 (Interior only)
•
Information above was used from Siemens Document Number 155-180P25.
ESPECIFICACIONES / SPECIFICATIONS
Fig. 8.o
31