Other UL requirements

1. Use 60/75 °C copper wire only.
2. Tighten terminals to 160 – 196 in-lbs. (18 – 22 Nm) for Main Input, 10.5 – 13.4 in-
3. Suitable for use on a circuit capable of delivering not more than 65.000 Amperes
4. The branch circuit protection shall be specified in the installation instructions.
5. Integral solid state short circuit protection does not provide branch circuit protec-
6. The Overload Protection trip current percentage (150 %).
7. WARNING – The opening of the branch circuit protective device may be an indica-
8. For use in Pollution Degree 2 environment.
9. For use only in a center earth TN supplied grid.
lbs. (1.2 – 1.5 Nm) Control in-lbs. or Nm.
rms symmetrical amperes when protected by when protected by fuses and circuit
breakersas described in the ratings section. This marking also includes the maxi-
mum voltage rating of the device.
tion. Branch circuit protection must be provided in accordance with the National
Electrical Code and any additional local codes.
tion that a fault current has been interrupted. To reduce the risk of fire or electrical
shock, current-carrying parts and other components of the controller should be
examined and replaced if damaged. If burnout of the current element of an overlo-
ad relay occurs, the complete overload relay must be replaced.